Figure 3-7
Figure 3-7 Effect of Changing the System Voltage Setting
Auto Stop Load: The auto stop load is set as a
percentage of full load.
approaches the fully charged state, the charge rate
slows, and the load on the generator set decreases.
The 6VSG will automatically stop when the load has
reached or fallen below the Auto Stop Load setting for
180 seconds (3 minutes). The default setting is 40%
load.
Load Limit (%): This setting limits the current output
to the maximum charge rate specified by the battery
manufacturer or load in the application. The default
setting is 100%, which gives the maximum current
Load Limit =
30
Section 3 Controller
As the battery bank
(Recommended charging voltage (VDC) x Maximum charging current (amps)) x 100
values shown in Figure 3-8.
manufacturer's recommended maximum charge rate
and see the Operation Manual for instructions if the
setting needs to be changed.
Figure 3-8
Nominal Voltage
System Voltage, VDC
Maximum Current at 100% Load
Limit, Amps
Figure 3-8
Maximum Charge Current at Default
Load Limit Setting of 100%
6000 watts
KPS_104
Refer to the battery
24V
36V
48V
27
40.5
54
222
148
111
TP-6844 1/13