Emerson PACSystems RX3i User Manual page 69

Rsti-ep dnp3 outstation module
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2911E
........................................
Object 12 (CROB) Memory Type %M (bit) Starting Address 1 Number of points 8
Object 41 (A Set) Memory Type %R (register) Starting Address 11 Number of points 4
Width of an Object 41 point 4 (bytes)
........................................
Point Push Memory Type %R (register) Starting Address 501 Number of Words Being Used 107
........................................
Last Point Push Response Sequence 0
internal Point Push stored last sequence 0
........................................
Options in [17]
Send Restart Bit on Power Up 1
Send Need Time Synch Bit 0
Point Push Data Needs a Y2k Adder 1
Data Link Layer Parameter Value 0
Application Link Layer Parameter Value 0
When 1, do not set the Point forced for Point Push points 0
When 1, do not assign default groups 0
When 1, do not assign object 01 to all be Push Points 0
When 1, do not assign object 10 to all be Push Points 0
When 1, do not assign object 30 to all be Push Points 0
When 1, do not assign object 40 to all be Push Points 0
When 1, Circular Buffer Enabled; when 0 Circular Buffer disabled; Current Value =0
........................................
Time to Process all points input read 36 (ms)
........................................
Interface Status and Debug Memory Type %w (register) Starting Address 1
........................................--------------------------------------------------------------------------------
>
Station Manager Status
Appendix B
Sep 2019
63