Control Word; Bit Table For The Control Word; Time Source Selection For Event Time Stamping - Emerson PACSystems RX3i User Manual

Rsti-ep dnp3 outstation module
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2911E
6.7

Control Word

Table 30:
Parameter
mComreq_Setup[24]
mComreq_Setup[25]

Bit Table for the Control Word

Table 31:
Bit
1
2-16
6.8

Time Source Selection for Event Time Stamping

Table 32:
Parameter
mComreq_Setup[18]
Configuration of DNP3 outstation Parameters
Value Description
0
0
Field
Description and values
Quality Force
When this bit is set to '0', the quality of the protocol objects for EDS001
module is set as Offline irrespective of CPU state. The state table follows:
CPU state
STOP
STOP
RUN
RUN
Note:
You can use this bit in runtime logic to interlock quality state with other
interlocks. If you set the mComreq_Setup[24] = 0, then Quality Force will not be
applicable and Quality will be driven by the CPU state.
Effective with firmware version 1.10, events are generated even when the
Quality flag is offline, and the appropriate quality status is then updated to
the Master. Prior to firmware version 1.10, the offline state of the Quality flag
prevented this.
Unused
Unused
Value Description
0
User selection of Time Source for time stamping of events.
1 – Selects CPU Time Source
0 – Selects local EDS001 Time Source.
Default value is set to 0.
The time synch command from the DNP3 master will set the local
time for both the EDS001 module and the CPU. However, the
timestamp for events will be based on the selection above.
Memory Type for Control word (16-bit)
Value: 8-%R, 10-%AI, 12-%AQ, 196-%W, 0-unused
Memory Address for Control word (16-bit)
Control word Parameters bits as shown in the below table
Quality Force Bit
Quality State
0
Offline
1
Offline
0
Offline
1
Online
Chapter 6
Sep 2019
53

Advertisement

Table of Contents
loading