Emerson PACSystems RX3i User Manual page 57

Rsti-ep dnp3 outstation module
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2911E
Bit
8
9
10
11
12
13
14
15
16
ST Text Example
*This example is from a Point Push SOE system.
//
mComreq_Setup[17] := 2#0001000001000110;
//
// Word 17 Option Bits
// Bit 1 == 1 Do not signal the master with a restart when starting.
// Bit 2 == 1 Do Not ask Master for time Set on startup
// Bit 3 == 1 if using Manual Point Feed with Year 2000+ dates, remove the 2k
// Bit 4 == 1 Data Link Layer can send multiple frames without confirmation
// Bit 5 == 1 Data Link Layer does not need confirmation
// Bit 6 == 1 Application Layer does not need confirmation
// Bit 7 == 1 Point Push points are NOT marked as forced when under PP control
// Bit 8 == 1 On Startup do no default objects to default class grouping.
// Bit 9 .unused
// Bit a .unused
// Bit b .unused
Configuration of DNP3 outstation Parameters
Field
Description and values
On startup default all points to a NULL grouping, so no event data is
Point Push
generated.
When '1', EDS will wait for 60 seconds before sending Link status requests
and if no DNP3 frames are received on the given session or there is no
response from DNP3 Master, then the EDS will automatically disconnect
Keep Alive
the connection with the Master.
Note:
It is available in EDS Firmware version-D303/150 and above.
unused
unused
unused
unused
When 1, do not enforce fixed buffers; instead place the data in a circular
SOE
buffer.
DI Object by default is set in Point Push mode, disabling automatic
Point Push
detection of data. However, initial state at power-up is captured for
points.
DO Object by default is set in Point Push mode, disabling automatic
Point Push
detection of data. However, initial state at power-up is captured for
points.
future
future
fedcba0987654321
Chapter 6
Sep 2019
51

Advertisement

Table of Contents
loading