// Bit c == 1 Circular Buffer Data will be kept in SOE mode.
// Bit d == 1 Object 01 Points, all part of Point Push at startup
// Bit e == 1 Object 10 Points, all part of Point Push at startup
// Bit f == 1 Object 30 Points, all part of Point Push at startup
// Bit g == 1 Object 40 Points, all part of Point Push at startup
6.6

Tuning Parameters

The EDS001 has an option area that can specify tuning parameters to the DNP3 application
for timing of DNP3 application and protocol layer specifications. The interface specifies a
20-word area that contains 32-bit values based on Table 29:

Interface Specification

These two words define a 20-word memory reference.
Note:
Table 28:
Parameter
mComreq_Setup[112]
mComreq_Setup[113]

Interface Definition

The Tuning data area has the following memory descriptions, in 32-bit Unsigned Integer
values
Table 29:
index
[000]
[001]
[002]
[003]
[004]
[005]
[006]
[007]
[008]
[009]
Configuration of DNP3 outstation Parameters
the memory address is limited to 65535.
Value
m-type
value
0
Unit
Description
ms
Amount of time in milliseconds that the clock is valid for. Default is 10 minutes.
ms
Data Link Layer Confirmation Response Time Out.
ms
Data Link Layer Receive Response Time Out.
Application Confirmation Time-Out Occurs. Default is 10 minutes
ms
(which has a value of 600,000).
N/A
unused
N/A
unused
N/A
unused
N/A
unused
N/A
unused
N/A
unused
Description
Memory Type for Option Setting Words
Value (decimal): 8-%R, 10-%AI, 12-%AQ, 196-%W, 0-
unused
Memory address for option parameter settings