SUMMER TEMPERATURE

This function sets a temperature for summer.
The summer temperature is adjusted in 0.5
degree increments from a minimum setting of -
3.5ºF (-19.0ºC) to a maximum setting of 99.5ºF
(39.5ºC). When the exterior temperature is
between the winter and summer temperature,
and none of the ventilation is activated, the air
TEMP.
inlet varies proportionally between the Summer
minimum position and the Winter minimum
position.
Adjusting the summer position:
rotate the Selector dial to position (12),
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
rotate the Selector dial to position (2),
rotate the Adjustor dial counterclockwise to
decrease
clockwise to increase it.
The summer position is displayed on the
DIP-1/115.
Example: The minimum summer position set by primary
function (2) is adjusted to 23%, and the summer
temperature
is
temperature reaches 70ºF and none of the ventilation
stages are activated, the air inlet opens at 23%.