The 12 secondary functions are:
•
1 Desired temperature for winter
•
2 Desired temperature for summer
•
3 Start position, when the first stage begins to operate at
minimum speed (unit 2)
•
4 End position, when the first stage runs at its maximum
speed (unit 2)
•
5 Start position, when the second stage begins to operate at
minimum speed (unit 2)
•
6 End position, when the second stage runs at its maximum
speed (unit 2)
•
7 Position, when the third stage begins to operate (unit 2)
•
8 Position, when the fourth stage begins to operate (unit 2)
•
9 Position, when the fifth stage begins to operate (unit 2)
•
10 Automatic calibration
•
11 Timer
•
12 Static room pressure display during the automatic
calibration
Select any one of these secondary mode functions by:
•
rotating the Selector dial to (12)
•
rapidly rotating the Adjustor dial back and forth to enter
in secondary mode
•
rotating the Selector dial from function (12)
other function.
When secondary functions 1 through 11 are selected the
status window displays a flashing value along with a
scrolling LED display. Selection of function 12 removes the
DIP-1/115 from the secondary function mode.
www.monitrol.com
CHAPTER 3 - USER'S GUIDE
to any
Page 17