Table 1; Cmm; Model Step; Low - LG ABNW85GB9A0 Installation Manual

Hide thumbs Also See for ABNW85GB9A0:
Table of Contents

Advertisement

How to Set E.S.P?
Ceiling Concealed Duct – Low static

Table 1

Model
ABNH09GL1A2
Model
ABNH12GL2A2
Model
ABNH18GL2A2
Model
ABNH24GL3A2
Note :
1. The above table shows the correlation between the air rates and E.S.P.
2. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
3. Table 1 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
36

CMM

Step
[m
3
/min]

LOW

5.5

MID

7

HIGH

9
CMM
Step
[m
3
/min]
LOW
7
MID
8.5
HIGH
10
CMM
Step
[m
3
/min]
LOW
10
MID
12.5
HIGH
15
CMM
Step
[m
/min]
3
LOW
12
MID
16
HIGH
20
Static Pressure [mmAq (Pa)]
0(0)
1(10)
32:01
32:02
69
76
81
87
97
103
Static Pressure [mmAq (Pa)]
0(0)
1(10)
32:01
32:02
78
82
87
91
96
100
Static Pressure [mmAq (Pa)]
0(0)
1(10)
32:01
32:02
96
100
109
113
120
124
Static Pressure [mmAq (Pa)]
0(0)
1(10)
32:01
32:02
89
95
102
108
125
131
2(20)
3(29)
Setting Value
32:03
32:04
83
91
94
101
108
117
2(20)
3(29)
Setting Value
32:03
32:04
87
93
94
100
103
109
2(20)
3(29)
Setting Value
32:03
32:04
103
109
117
123
129
134
2(20)
3(29)
Setting Value
32:03
32:04
102
106
115
125
136
141
4(39)
5(49)
32:05
32:06
101
111
109
117
124
131
4(39)
5(49)
32:05
32:06
100
107
108
116
117
125
4(39)
5(49)
32:05
32:06
117
125
130
137
141
147
4(39)
5(49)
32:05
32:06
120
130
131
139
144
147