4. Please connect indoor unit and remote controller using connection cable.
12 V
Red
Signal
Yellow
GND
Black
5. Please use extension cable if the distance between wired remote controller and indoor unit is more
than 10 m.
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in
the temperature sensor.)
Do not install the cable to be 50 m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote
controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.

Wired remote controller installation

• Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the
remote controller about 5 ft(1.5 m) above the floor in an area with good air circulation at an average temperature.
Do not install the remote controller where it can be affected by:
- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote
controller LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)
24
Sun ray contact area
no
no
Fig.1 Typical locations for remote controller
Please check if connector is normally connected.
Connecting cable
Direct
yes
no