The product is designed to meet the following type tests as listed in Table 4-1.
Table 4-1: Type Tests
CATEGORY
EMC Emissions
EN 61326-
1:2006
EMC Immunity
EN 61326-
1:2006
IEC 61000-6-5:
2015
Environmental
Tests
Safety
Note: Bushing monitoring falls outside the scope of UL61010-1 and CSA C22.2 No.
*5
61010-1 and cannot be included in any third-party certification for North
America.
MA-041 – DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
STANDARD
Performance
Criteria
CISPR 11
A
FCC Part 15
Meets the
requirements of A
EN 61000-3-2
A
EN 61000-4-2
B
EN 61000-4-3
A
EN 61000-4-4
B
EN 61000-4-5
B
EN 61000-4-6
A
EN 61000-4-8
A
EN 61000-4-11
B, C
IEC 61000-4-16
A
IEC61000-4-17
A
IEC61000-4-18
B
EN 60255-5
5 kV, 2 kV &
500 V DC
IEC 60068-2-1
−40 °C
IEC 60068-2-2
55 °C
IEC 60068-2-6
10 – 500 Hz,
0.5 g operation
10 – 500 Hz,
1 g endurance
IEC 6IEC0068-2-
55 °C, 95% RH
30
IEC60068-2-6
IEC60068-2-27
EN 60529
IP56
IEC 61010-1
EN 61010-1
UL61010-1
*5
CSA C22.2 No.
61010-1
*5
TEST
Radiated & Conducted Emissions
Radiated & Conducted Emissions
Harmonic Current Emissions
Limits
Electrostatic Discharge
Electromagnetic Field Immunity
Electrical Fast Transients
Surge Immunity
Conducted RF Immunity
Magnetic Field Immunity
Voltage Dips & Interruptions
Mains frequency voltage
Ripple on DC power supply
Damped oscillatory wave
Impulse, Dielectric & Insulation
resistance testing
Cold
Dry Heat
Vibration
Damp Heat
Vibration (sinusoidal)
Vibration (bump, shock)
Degree of Protection