COMPLIANCE

The product is designed to meet the following type tests as listed in Table 4-1.
Table 4-1: Type tests
CATEGORY
EMC Emissions
EN 61326-
1:2006
EMC Immunity
EN 61326-
1:2006
IEC 61000-6-5:
2015
Environmental
Safety
MA-025 – DGA 900 Operator Guide – Rev 2.0
STANDARD
CLASS/LEVEL
CISPR 11
A
FCC Part 15
Meets the
requirements of A
EN 61000-3-2
A
EN 61000-4-2
IV
EN 61000-4-3
III
EN 61000-4-4
III
EN 61000-4-5
III
EN 61000-4-6
III
EN 61000-4-8
IV & V
EN 61000-4-11
III
IEC 61000-4-12
2.5 kV & 1 kV
IEC 61000-4-16
A
5 kV, 2 kV &
EN 60255-5
500 V DC
IEC 60068-2-1
−40 °C
IEC 60068-2-2
55 °C
IEC 60068-2-6
10 – 500 Hz,
0.5 g operation
10 – 500 Hz,
1 g endurance
IEC 60068-2-30
55 °C, 95% RH
EN 60529
IP56
IEC 61010-1
EN 61010-1
TEST
Radiated & Conducted Emissions
Radiated & Conducted Emissions
Harmonic Current Emissions
Limits
Electrostatic Discharge
Electromagnetic Field Immunity
Electrical Fast Transients
Surge Immunity
Conducted RF Immunity
Magnetic Field Immunity
Voltage Dips & Interruptions
Oscillatory Wave
Mains frequency voltage
Impulse, Dielectric & Insulation
resistance testing
Cold
Dry Heat
Vibration
Damp Heat
Degree of Protection
2010
2010
12-Apr-19
Page 14 of 92

Hide quick links:

Advertisement

Table of Contents
loading