Compliance; Table 5-1: Type Tests - GE Kelman TRANSFIX 1.6 Installation Manual

Transformer oil dissolved gas and moisture monitor
Table of Contents

Advertisement

5 COMPLIANCE

The product meets the following type tests as listed in Table 5—1:
Category
Standard
EMC Emissions –
CISPR 11
EN 61326-1:2006
FCC Part 15
EN 61000-3-2
EMC Immunity –
EN 61000-4-2
EN 61326-1:2006
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
IEC 61000-4-9
IEC 61000-4-10
EN 61000-4-11
IEC 61000-4-12
IEC 61000-4-18
EN 61000-3-3
EN 60255-5
Environmental
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-6
IEC 60068-2-30
EN 60529
Safety
IEC 61010-1
EN 61010-1
UL 61010-1
MA-001 – TRANSFIX-family Installation Manual – Rev 3.0
Table 5—1: Type tests
Class/Level
A
A
A
IV
III
III
III
III
IV & V
X
X
III
X 2.5 kV & 1kV
X
Pst 10 min, Plt 120 min
5 kV, 2 kV & 500 V DC
−40 °C
55 °C
10 – 150 Hz, 0.5 g operation
10 – 150 Hz, 0.5 g endurance
55 °C, 95% RH
IP55
Test
Radiated & Conducted Emissions
Radiated & Conducted Emissions
Harmonic Current Emissions
Limits
Electrostatic Discharge
Electromagnetic Field Immunity
Electrical Fast Transients
Surge Immunity
Conducted RF Immunity
Magnetic Field Immunity
Pulsed Magnetic Field Immunity
Damped Oscillatory Magnetic
Field Immunity
Voltage Dips & Interruptions
Oscillatory Wave
Damped Oscillatory Wave
Voltage fluctuations & flicker
Impulse, Dielectric & Insulation
resistance testing
Cold
Dry Heat
Vibration
Damp Heat
Degree of Protection
2010
2010
2012
18-Jan-16
Page 11 of 55