Figure 9-32: Configure > Save last measured data > as "open" calibration
Select File > Save As and type the filename calibOpen as shown in Figure 9-33.
Figure 9-33: Save As "calibOpen"
9.8.2.2.2 Short Circuit Test
Connect the clips to each other as shown in Figure 9-34.