GE Kelman DGA 900 Plus Installation & Commissioning Manual page 58

Transformer monitoring system
Table of Contents

Advertisement

Figure 9-32: Configure > Save last measured data > as "open" calibration
Select File > Save As and type the filename calibOpen as shown in Figure 9-33.
Figure 9-33: Save As "calibOpen"
9.8.2.2.2 Short Circuit Test
Connect the clips to each other as shown in Figure 9-34.
MA-041 – DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
4-Mar-22
Page 58 of 99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents