GE Kelman DGA 900 Plus Installation & Commissioning Manual page 28

Transformer monitoring system
Table of Contents

Advertisement

Figure 8-1: OLTC Monitor wiring – three phase
Note:
Top oil temperature isn't installed if the top oil temperature of the thermal card
is available.
Note:
See Section 8.2 for the Power converter wiring.
8.1.2.2 Wiring (single phase AC only)
The OLTC motor torque requires the installation of a loop-powered split core CT to
provide the product with a 4-20 mA input. Figure 8-2 shows the wiring plan and the 4-20
mA output connected to the product.
Note:
Contact GE for specific details on the implementation. The installation position
within the motor circuit does depend on the configuration, for example, if DC
braking is deployed.
MA-041 – DGA 900 Plus - Installation & Commissioning Manual - Rev 1.1
4-Mar-22
Page 28 of 99

Hide quick links:

Advertisement

Table of Contents
loading