Configuration (continued)
Jumpers
Jumper P1 sets the Autoforward mode to determine how data traffic is handled before the BNIC
CPU is online.
Setting 1-2:
This is the recommended default setting. In this mode the BNIC does not allow traffic to be
routed through the switch until the BNIC CPU is online and running.
LED Indicators
Table 4 lists the different LED indicators found on the BNIC that are troubleshooting aids.
LED
Port A (LED 9)
Port B (LED 6)
Port C (LED 2)
Port D (LED 1)
X (LED 5)
Y (LED 4)
Z (LED 3)
Offline (LED 7)
Reset (LED 10)
(see Figure 2 for
positioning)
Earth Fault (LED 8)
Table 4. BNIC LED Descriptions
Description
Port Status LED
Card Status LED
Offline Indication
Reset Indication
Earth Fault Indication
on Port A
Port A
Port B
Port A
Port B
Figure 4. LED positioning
5
firealarmresources.com
BNIC Installation and Programming Manual
Signification
OFF = No Connection
ON Steady = Non-active connection
ON Blinking = Active connection
Used for manufacturing and development only, not
used for installed BNIC
ON = Offline (not communicating with 4100ES
Master Controller Card)
OFF = Normal Operation
ON = BNIC is in reset
Off = Normal Operation
ON = Earth Fault detected on Port A
OFF = No Earth Fault detected
Port C
Port D
Port C
Port D