Project Planning Manual | Rexroth IndraControl VAU01.1S
4
Technical Data
4.1
Degree of Protection and Weight
4.2
Input and Output Voltage
4.2.1
+24-V Input Voltage
4.2.2
Output Voltage
Degree of protection
Weight
Fig.4-1:
Degree of protection and weight
Nominal input voltage
Input voltage range
Noise and surge immunity
Power consumption for U
N
Input fuse
Reverse voltage protection
Voltage rise of the supply voltage when
switching on
Voltage drop of the supply voltage when
switching off
Switch-on threshold
Switch-off threshold
Max. power consumption
Fig.4-2:
+24-V input voltage
Nominal output voltage
Output voltage range
Current output for U
N
Switching time
Bridging time
Max. output power
Fig.4-3:
Output voltage
The maximum power consumption of the connected control cabinet
must not exceed the maximum output power of the UPS.
Electric Drives
| Bosch Rexroth AG
and Controls
IP 20
3.5 kg
24 VDC
24 VDC +20 %, -15 %
Umax = 35 V (at t < 100 ms)
Max. 12 A (2 A for charging the battery)
None
Yes
Max. 500 ms (0 V to UN)
Max. 500 ms (UN to 0V)
15.5 V ±5 %
20.2 V ±5 %
240 W (48 W for charging the battery)
24 VDC
24 VDC +20 %, -15 %
Max. 10 A
< 1 ms
Max. 3 minutes
240 W
13/43
Technical Data