Fuses F1; Rotary Switch S1; General Information - Bosch Rexroth IndraControl VAU01.1S Project Planning Manual

Ups with rs232 interface
Hide thumbs Also See for Rexroth IndraControl VAU01.1S:
Table of Contents

Advertisement

26/43
Bosch Rexroth AG | Electric Drives
Interfaces, Display and Operating Components
LED
Display
Designa‐
tion
4
Batt.
LED green Battery is charged
charg.
LED OFF
or flashing
5
Batt.
LED red
low
(more than
500 ms)
LED red
(500 ms
after
switch-on)
LED off
6.5

Fuses F1

6.6

Rotary Switch S1

6.6.1

General Information

and Controls
Meaning
Battery is charged
Battery is either discharged, not connected or
fuse F1 (front side) is released.
(The LED is triggered by the UPS software)
Battery is defective or the deep discharge thresh‐
old of 18 V is reached.
(The LED is independently triggered by the UPS
software)
Normal mode
Fig.6-12:
Description of the LEDs
The FKS fuse (20 A, 32 V) can be reached via the front panel (F1 connection).
The battery is secured by fuse F1. Without fuse F1 the UPS cannot be operated.
With the rotary switch you can set different UPS times . By using the switch
positions from 0 to 3 it is possible to change the UPS time in steps of one minute.
The UPS time is the time period in which the connected device is provided with
output voltage of the UPS - after the switch off of the input voltage. The switch
position is in the delivery status "1".
Fig.6-13:
Position of rotary switch S1
Rexroth IndraControl VAU01.1S | Project Planning Manual
Measure
Guaranteed UPS bridging time cannot be
kept
UPS is ready for operation
Keep the UPS switched on so that the bat‐
tery can be loaded (max. 5 h). Check the
battery and, if necessary, replace it, or
check fuse F1 if the LED continues flash‐
ing.
Check if the battery is connected to the
printed circuit board.
Keep the UPS switched on, so that the bat‐
tery can be loaded (max. 5 h). If the LED
continues flashing after this time, check
and/or change the battery.
-