Danger of faulty or insufficient grid power supply.
This can result in severe personal injury and damage to property.

Charging cables

Danger due to charging cables lying around.
This can result in severe personal injury and damage to property. Personnel can
get caught or trip on unplugged, loose cables
Danger if the active charging process is interrupted by disconnecting the char-
ging plug.
This can result in severe personal injury and damage to property. The resulting
sparks can ignite the charging gases that form during charging and cause a fire or
explosion
Correct routing
of the mains/
charging cables
Danger due to overheating as a result of incorrectly laid mains/charging cables.
Risk of damage to the components.
WARNING!
The requirements for the grid power supply according to the "Technical data"
chapter must be fulfilled.
WARNING!
Lay charging cables so that no one can trip over them or get caught on them.
WARNING!
When charging is complete, wind up the charging cables or place them on
the cable holder, if available.
CAUTION!
Lay the mains/charging cable without a loop.
Do not cover the mains/charging cable.
Charging cables longer than 5 m (16 ft. 4.85 in.) must be laid individually (no
bundling).
Charging cables longer than 5 m (16 ft. 4.85 in.) can have an increased sur-
face temperature (be aware of hot surfaces).
In the following cases, pay special attention that the surface temperature of
the charging cables does not exceed 80 °C (176 °F):
- Ambient temperature is 30 °C (86 °F) or more
- Cross-section of the charging cable is 95 mm
- Length of the charging cable is 5 m (16 ft. 4.85 in.) or more
The mains/charging cable may only be replaced by a qualified electrician.
2
or more
13