Tyco RSV-1 Manual

Tyco RSV-1 Manual

Shut-off valve, 1 inch and 2 inch (dn25 and dn50) for dual-purpose residential water suppl

Advertisement

Quick Links

RAPID RESPONSE Model RSV-1 Residential
Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for
Dual-Purpose Residential Water Supply
General
Description
The TYCO RAPID RESPONSE Model
RSV-1 Residential Shut-Off Valves
are intended for use in dual-purpose
residential water supply piping that
serves both domestic and residential
fi re protection sprinkler system needs.
The 1 Inch (DN25) Valve is intended
for NFPA 13D system needs, whereas
the 2 Inch (DN50) Valve is intended for
systems designed in accordance with
either NFPA 13D or NFPA 13R.
When a fi re sprinkler operates, the
Model RSV-1 Residential Shut-Off
Valve automatically shuts off water
fl ow to the domestic system and di-
verts the available water supply to the
fi re sprinkler system. Consequently,
when the Model RSV-1 Valve is uti-
lized, the system designer does not
need to add the domestic fl ow de-
mand to the fi re sprinkler system fl ow
demand, as would otherwise be re-
quired by NFPA 13R.
Consider use of the Model RSV-1
Residential Shut-Off Valve when either
the water supply cannot adequately
provide for both the domestic design
demand and the fi re sprinkler fl ow de-
mand, or it is necessary to increase
the effectiveness of the fi re sprinkler
system by automatically shutting off
the domestic fl ow.
The Model RSV-1 Residential Shut-
Off Valve maximizes the effective use
of an existing water supply. Therefore,
in areas with limited water supplies, it
may eliminate the need to add costly
pumps, pressurized reservoirs, or elec-
trically operated domestic shut-off
valves. The Model RSV-1 Valve has a
built-in check valve in the fi re sprinkler
system outlet that eliminates the need
for a separate check valve. Also, the
Model RSV-1 Valve automatically re-
sets, thereby eliminating the need for
valve disassembly after a fi re sprinkler
system test or operation.
Page 1 of 8
NOTICE
The Model RSV-1 Residential Shut-Off
Valves described herein must be installed
and maintained in compliance with this
document, as well as with the applicable
standards of the National Fire Protection
Association, in addition to the standards
of any authorities having jurisdiction.
Failure to do so may impair the integrity
of this device.
The owner is responsible for maintaining
their fi re protection system and devices in
proper operating condition. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Technical
Data
Approvals
• The 1 Inch (DN25) Model RSV-1 Resi-
dential Shut-Off Valve is UL and C-UL
Listed. It is suitable for use in water
supply arrangements for residential
fi re sprinkler systems designed per
NFPA 13D.
• The 2 Inch (DN50) Model RSV-1 Resi-
dential Shut-Off Valve is UL and C-UL
Listed and NSF-61 Annex G Approved.
It is suitable for use in water supply
arrangements for residential fi re sprin-
kler systems designed per NFPA 13D
or 13R.
Maximum Pressure
175 psi (12,1 bar)
Weight
1 Inch (DN25): 11 lbs. (5 kg)
2 Inch (DN50): 29 lbs. (11 kg)
Pressure Loss
Refer to Figures 5 and 6.
Patents
2 Inch (DN50) Model RSV-1 Valve:
Patent Pending
March 2012
+1-401-781-8220
Technical Services
www.tyco-fi re.com
Physical Characteristics
Refer to Figures 3 and 4.
• 1 Inch (DN25) Valve
Body . . . . . . . . . . . . . .Copper Alloy
Top and
Bottom Cover . . . . . . .Copper Alloy
Upper Cap . . . . . . . . . . . . . . . Brass
Bottom Seal. . . . . . . . . . . . . . Brass
Piston. . . . . . . . . . Glass Reinforced
Differential
Ring . . . . . . . . . . . Glass Reinforced
Sleeve . . . . . . . . . Glass Reinforced
Upper and
Lower Seals . . . . . . . . . . . . . . EPDM
O-Rings . . . . . . . . . . . . . . . . Buna-N
Piston Spring . . . . . . Stainless Steel
Piston Screws . . . . . Stainless Steel
Cap Screw . . . . . . . . Stainless Steel
• 2 Inch (DN50) Valve
Body and
Cover . . . . . . . . . . . . . .Copper Alloy
Piston Insert . . . . . . . .Copper Alloy
Bottom Seal. . . . . . . . .Copper Alloy
Piston Cover . . . . Glass Reinforced
Insert Sleeve . . . . Glass Reinforced
Piston Seal. . . . . . . . . . . . . . . EPDM
O-Rings . . . . . . . . . . . . . . . . . EPDM
Piston Spring . . . . . . Stainless Steel
Piston Nut . . . . . . . . Stainless Steel
Retainer Ring. . . . . . Stainless Steel
800-381-9312
Polyphenylene Oxide
Polyphenylene Oxide
Polyphenylene Oxide
Polyphenylene Oxide
Polyphenylene Oxide
TFP980

Advertisement

Table of Contents
loading

Summary of Contents for Tyco RSV-1

  • Page 1 Upper Cap ....Brass lized, the system designer does not • The 1 Inch (DN25) Model RSV-1 Resi- Bottom Seal....Brass...
  • Page 2: Design Criteria

    TEST CONNECTION WATERFLOW located in the water supply upstream DETECTOR of the Model RSV-1 Valve as shown (FIRE ALARM) in Figure 1. Should local regulations ALARM TEST require the backfl ow prevention de- CONNECTION...
  • Page 3: Operating Principles

    8-3/16" Upper Sleeve mestic water usage. (208,0 mm) Sleeve Spring When the Model RSV-1 Valve is in the 10 - Differential 4-15/16" normal standby position as shown in (125,4 mm) Ring Figures 7 and 8, the Piston Assembly,...
  • Page 4 Internal By-Pass Restriction, when mine the minimum possible residual to the full up position, only a small the Model RSV-1 Valve is in the op- (fl owing) pressure available to the fi re amount of water is permitted to trickle erated position, is less than 1/4 GPM sprinkler system.
  • Page 5 RESTRICTION DOMESTIC SEAT DOMESTIC SUPPLY SUPPLY SEAT PORT PORT SUPPLY SUPPLY STANDBY OPERATED FIGURE 7 STANDBY AND OPERATED POSITIONS FOR 1 INCH (DN25) MODEL RSV-1 VALVE TO FIRE SPRINKLERS FIRE FIRE SPRINKLER SPRINKLER PISTON PISTON PORT PORT ASSEMBLY ASSEMBLY FIRE...
  • Page 6: Installation

    Make no attempt to repair any Model arrangement using the TYCO RAPID Test Connection in the fi re sprinkler RSV-1 Valve component in the fi eld. The RESPONSE Model RSV-1 Residential system, close all drain valves and Model RSV-1 Valve is not fi eld-repairable.
  • Page 7: Limited Warranty

    This RSV-1 Residential Shut-Off Valve, P/N warranty will expire ten (10) years from 4. Reset the Model RSV-1 Valve in ac- 52-540-1-001. date of shipment by TFPP. No war- cordance with the Valve Setting Pro- ranty is given for products or com- cedure described in this data sheet.
  • Page 8 TFP980 Page 8 of 8 Copyright © 2012 Tyco Fire Protection Products. All rights reserved. TEFLON is trademark of The DuPont Corporation.