Preaction system with model dv-5 deluge valve double interlock — electric/pneumatic actuation 1-1/2 thru 8 inch
Hide thumbs Also See for DN40:

Advertisement

Quick Links

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Preaction System with Model DV-5 Deluge Valve
Double Interlock — Electric/Pneumatic Actuation
1-1/2 thru 8 Inch (DN40 and DN200)
General
Description
The Model DV-5 Double Interlock Pre-
action System with Electric/Pneumatic
Actuation (Fig. 1) is designed for use
in applications, such as refrigerated
areas, requiring the maximum degree
of protection against inadvertent flood-
ing of the sprinkler system piping.
The Model DV-5 Double Interlock Pre-
action System with Electric/Pneumatic
Actuation utilizes a Model DV-5 Deluge
Valve and a Riser Check Valve. The
Riser Check Valve (that does not re-
quire the use of priming water) isolates
the Deluge Valve from the system air
pressure. The releasing trim for the
Deluge Valve utilizes a Solenoid Valve
and a Dry Pilot Actuator in a series
configuration. The system air pressure
holds the Dry Plot Actuator closed,
whereas the Solenoid Valve remains
closed until it is electrically energized
by a Deluge Valve Releasing Panel
(automatic control unit). The Releas-
ing Panel is operated by either a fire
detection device or manual electric
pull station.
In order for the Double Interlock Pre-
action System to automatically actu-
ate, two independent events must oc-
cur. The deluge valve releasing panel
must operate and open the Solenoid
Valve upon automatic operation of the
electric fire detection initiating circuit
or manual operation of the electric-
manual pull initiating circuit, and the
sprinkler system piping must lose air
pressure due to operation of one or
more sprinklers.
The Double Interlock Preaction Sys-
tem will automatically actuate only
when both the Dry Pilot Actuator and
the Solenoid Valve are open at the
same time. Accidental opening of just
the Dry Pilot Actuator (for example: a
lift truck accidentally dislodges a sprin-
kler), or just energizing the Solenoid
Valve (for example: an accidental op-
Page 1 of 16
eration of an electric pull station), will
only cause an alarm, and will not actu-
ate the system or flood the sprinkler
system piping.
The Model DV-5 Deluge Valve (de-
scribed in Technical Data Sheet
TFP1305) is a diaphragm style valve
that depends upon water pressure in
the Diaphragm Chamber to hold the
Diaphragm closed against the water
supply pressure. When the DV-5 Valve
is set for service, the Diaphragm
Chamber is pressurized through the
trim connections from the inlet side of
the system's main control valve, for
MARCH, 2005
example an O.S.&Y. gate valve or but-
terfly valve (Fig. 1).
Operation of the Solenoid Valve and
Dry Pilot Actuator at the same time
releases water from the Diaphragm
Chamber faster than it can be replen-
ished through the 1/8 inch (3,2 mm)
Priming Supply Restriction (Item 7 -
Fig. 2A) in the diaphragm supply con-
nections. This results in a rapid pres-
sure drop in the Diaphragm Chamber
below the valve trip point. The water
supply pressure then forces the Dia-
phragm open permitting water to flow
(TEXT CONTINUED ON PAGE 9)
TFP1460

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DN40 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco DN40

  • Page 1 Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Preaction System with Model DV-5 Deluge Valve Double Interlock — Electric/Pneumatic Actuation 1-1/2 thru 8 Inch (DN40 and DN200) General Description The Model DV-5 Double Interlock Pre- action System with Electric/Pneumatic Actuation (Fig.
  • Page 2 TFP1460 Page 2 of 16 17 - Model DV-5 Deluge Valve System Drain Valve (N.C.) System Shut-Off Valve (N.O.) 10 - 18 - Main Control Valve (N.O.) Main Drain Valve (N.C.) Air Pressure Gauge (Shown at Rear of Valve) 19 - Diaphragm Chamber Supply Automatic Air/Nitrogen Supply 11 -...
  • Page 3 TFP1460 Page 3 of 16 15 - Model DV-5 Deluge Valve Water Supply Pressure Gauge Deluge Valve Releasing Panel (Shown at Front of Valve) 16 - Main Control Valve (N.O.) Riser Check Valve Diaphragm Chamber Pressure 17 - Diaphragm Chamber Supply System Shut-Off Valve (N.O.) Gauge (Shown at Front of Valve) Control Valve (N.O.)
  • Page 4 Route all Tubing to Drip Funnel, CH: Common Hardware. Item 15. FIGURE 2A — PART 1 OF 3 1-1/2 and 2 INCH (DN40 and DN50) MODEL DV-5 DELUGE VALVES DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM (52-478-X-127) — EXPLODED VIEW —...
  • Page 5 TFP1460 Page 5 of 16 DESCRIPTION QTY. DESCRIPTION QTY. DESCRIPTION QTY. 300 psi/ 2000 kPa 3/4" Union ... . P3 Model DP-1 Dry Pilot Water Pressure Gauge . . 92-343-1-005 1/4"...
  • Page 6 TFP1460 Page 6 of 16 DESCRIPTION QTY. DESCRIPTION QTY. DESCRIPTION QTY. 300 psi/ 2000 kPa 1" x 1/2" 90° Elbow ..1/2" Tubing Connector Water Pressure Gauge . . 92-343-1-005 1" x 3/4" x 1" Tee .
  • Page 7 MAIN DRAIN 1/2 INCH NPT (NORMALLY SHOWN CONNECTION CONNECTION FROM OPEN) (SIZED PER TABLE) WATER SUPPLY FIGURE 2B 1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVES DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM — OPERATIONAL COMPONENTS —...
  • Page 8: Left View

    (FIELD FABRICATED) MAIN 2" NPS 1-1/4" NPS CONTROL DRAIN DRAIN VALVE LEFT VIEW FRONT VIEW FIGURE 3 1-1/2 thru 8 INCH (DN40 thru DN200) MODEL DV-5 DELUGE VALVES DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION TRIM — NOMINAL INSTALLATION DIMENSIONS —...
  • Page 9: Technical Data

    AFFF sys- NOTE tems. 1-1/2 inch (DN40) risers utilize a 2 inch (DN50) Riser Check Valve in combina- NOTE tion with the 1-1/2 inch (DN40) Model When the system pressure is greater DV-5 Deluge Valve.
  • Page 10 TFP1460 Page 10 of 16 FLOW RATE IN LITRES PER MINUTE (LPM) (1 GPM = 3,785 LPM) 1000 2000 3000 5000 7000 10000 15.0 1,000 0,900 0,800 0,700 10.0 0,600 0,500 0,400 0,300 0,200 0,100 0,090 0,080 0,070 0,060 0,050 0,040 0,030 1000...
  • Page 11: Installation

    Electric/Pneumatic Actuation is listed or approved (as appropriate) in- shown in Graph A as a function of the 1-1/2 inch (DN40) risers utilize a 2 inch dicating valve with a supervisory anticipated water supply pressure. It is (DN50) Riser Check Valve in combina-...
  • Page 12 TFP1460 Page 12 of 16 must be installed with smooth bends Automatic Drain Valve (4, Fig. 2A) is to to a temperature greater than their that will not restrict flow. be temporarily replaced with a 1/2 inch maximum rated ambient must also be NPT plug, the 3/32 inch Vent Fitting (17 replaced.
  • Page 13: Care And Maintenance

    TFP1460 Page 13 of 16 drain connection. Observe the Auto- authorities and all personnel who may Care and matic Drain Valve for leaks. If there are be affected. leaks, determine/correct the cause of Maintenance Before closing a fire protection system the leakage problem.
  • Page 14: Limited Warranty

    Quarterly Waterflow Alarm Test Authorities Having Jurisdiction. Mate- Step 12. Open (energize) the Solenoid Procedure rials found by Tyco Fire Products to be Valve by operating the deluge valve Testing of the system waterflow alarms defective shall be either repaired or releasing panel, and verify the follow- must be performed quarterly.
  • Page 15: Ordering Procedure

    P/N 59-590-1-080 NOTE COUPLING (SELECT ONE) 1-1/2 inch (DN40) risers utilize a 2 inch P/N’s are for American Standard Grooved Connections. For other configurations and (DN50) Riser Check Valve in combina- finishes refer to Technical Data Sheet TFP1830 and TFP1880. A coupling to attach the tion with the 1-1/2 inch (DN40) Model Riser Check Valve to the outlet of the Deluge Valve must be separately ordered.