Model RSV-1 Residential Shut-Off Valve
1 Inch and 2 Inch (DN25 and DN50) for
Dual-Purpose Residential Water Supply
General
Description
The TYCO RAPID RESPONSE Model
RSV-1 Residential Shut-Off Valves
are intended for use in dual-purpose
residential water supply piping that
serves both domestic and residential
fire protection sprinkler system needs.
The 1-Inch (DN25) Valve is intended
for NFPA 13D system needs, whereas
the 2-Inch (DN50) Valve is intended for
systems designed in accordance with
either NFPA 13D or NFPA 13R.
When a fire sprinkler operates, the
Model RSV-1 Residential Shut-Off
Valve automatically shuts off water
flow to the domestic system and di-
verts the available water supply to the
fire sprinkler system. Consequently,
when the Model RSV-1 Valve is uti-
lized, the system designer does not
need to add the domestic flow de-
mand to the fire sprinkler system flow
demand, as would otherwise be re-
quired by NFPA 13R.
Consider use of the Model RSV-1
Residential Shut-Off Valve when either
the water supply cannot adequately
provide for both the domestic design
demand and the fire sprinkler flow de-
mand, or it is necessary to increase
the effectiveness of the fire sprinkler
system by automatically shutting off
the domestic flow.
The Model RSV-1 Residential Shut-
Off Valve maximizes the effective use
of an existing water supply. Therefore,
in areas with limited water supplies, it
may eliminate the need to add costly
pumps, pressurized reservoirs, or elec-
trically operated domestic shut-off
valves. The Model RSV-1 Valve has a
built-in check valve in the fire sprinkler
system outlet that eliminates the need
for a separate check valve. Also, the
Model RSV-1 Valve automatically re-
sets, thereby eliminating the need for
valve disassembly after a fire sprinkler
system test or operation.
Page 1 of 8
www.tyco-fire.com
NOTICE
The Model RSV-1 Residential Shut-Off
Valves described herein must be installed
and maintained in compliance with this
document, as well as with the applicable
standards of the National Fire Protection
Association, in addition to the standards
of any authorities having jurisdiction.
Failure to do so may impair the integrity
of this device.
Owners are responsible for maintaining
their fire protection system and devices in
proper operating condition. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Technical
Data
Approvals
• The 1-Inch (DN25) Model RSV-1 Resi-
dential Shut-Off Valve is UL and C-UL
Listed and NSF-61 Annex G Approved.
It is suitable for use in water supply
arrangements for residential fire sprin-
kler systems designed per NFPA 13D.
• The 2-Inch (DN50) Model RSV-1 Resi-
dential Shut-Off Valve is UL and C-UL
Listed and NSF-61 Annex G Approved.
It is suitable for use in water supply
arrangements for residential fire sprin-
kler systems designed per NFPA 13D
or 13R.
Maximum Pressure
175 psi (12,1 bar)
Weight
1-Inch (DN25): 11 lbs. (5 kg)
2-Inch (DN50): 29 lbs. (11 kg)
Pressure Loss
Refer to Figures 7 and 8.
Patents
2-Inch (DN50) Model RSV-1 Valve:
Patent Pending
DECEMBER 2010
Physical Characteristics
Refer to Figures 3 and 4.
• 1-Inch (DN25) Valve
Body . . . . . . . . . . . . . .Copper Alloy
Top and
Bottom Cover . . . . . . .Copper Alloy
Upper Cap . . . . . . . . . . . . . . . Brass
Bottom Seal. . . . . . . . . . . . . . Brass
Piston. . . . . . . . . . Glass Reinforced
Polyphenylene Oxide
Differential
Ring . . . . . . . . . . . Glass Reinforced
Polyphenylene Oxide
Sleeve . . . . . . . . . Glass Reinforced
Polyphenylene Oxide
Upper and
Lower Seals . . . . . . . . . . . . . . EPDM
O-Rings . . . . . . . . . . . . . . . . Buna-N
Piston Spring . . . . . . Stainless Steel
Piston Screws . . . . . Stainless Steel
Cap Screw . . . . . . . . Stainless Steel
• 2-Inch (DN50) Valve
Body and
Cover . . . . . . . . . . . . . .Copper Alloy
Piston Insert . . . . . . . .Copper Alloy
Bottom Seal. . . . . . . . .Copper Alloy
Piston Cover . . . . Glass Reinforced
Polyphenylene Oxide
Insert Sleeve . . . . Glass Reinforced
Polyphenylene Oxide
Piston Seal. . . . . . . . . . . . . . . EPDM
O-Rings . . . . . . . . . . . . . . . . . EPDM
Piston Spring . . . . . . Stainless Steel
Piston Nut . . . . . . . . Stainless Steel
Retainer Ring. . . . . . Stainless Steel
TFP980

Advertisement

Table of Contents
loading

Summary of Contents for Tyco RAPID RESPONSE RSV-1

  • Page 1 The Model RSV-1 Residential Shut-Off Description Valves described herein must be installed and maintained in compliance with this The TYCO RAPID RESPONSE Model document, as well as with the applicable RSV-1 Residential Shut-Off Valves standards of the National Fire Protection...
  • Page 2: Design Criteria

    In order for the 2-Inch (DN50) Model mum expected value. RSV-1 Valve to operate automati- The TYCO Model RSV-1 Residential The minimum single sprinkler flow cally at sprinkler activation, the fire Shut-Off Valve must be installed verti-...
  • Page 3: Operating Principles

    Principles 3-5/8" DIA. FIRE (92,1 mm) SPRINKLER Components: PORT, 1" NPT When a fire sprinkler activates dur- Body ing domestic usage, the TYCO Model Top Cover RSV-1 Residential Shut-Off Valve Screw, automatically shuts off flow to the Upper Cap domestic system and diverts the avail-...
  • Page 4 TFP980 Page 4 of 8 As indicated above, domestic system is equal to or greater than 12.5 GPM When the Domestic Control Valve is usage can reduce the pressure avail- (47,3 LPM) for the 1-Inch Valve or 8 closed, the Internal By-Pass Restric- able to the fire sprinkler system.
  • Page 5 TFP980 Page 5 of 8 FIRE FIRE TO FIRE SPRINKLER PISTON PISTON SPRINKLER SPRINKLERS PORT ASSEMBLY ASSEMBLY PORT FIRE FIRE FIRE SPRINKLER SPRINKLER SPRINKLER SEAT SEAT FLOW PASSAGE DOMESTIC PORT DOMESTIC DOMESTIC DOMESTIC PORT FLOW INTERNAL PASSAGE BY-PASS RESTRICTION DOMESTIC SEAT DOMESTIC SUPPLY...
  • Page 6: Installation

    Perform steps 1 through 9 when initial- to a public water supply is usually subject ly filling the fire sprinkler and domestic for the TYCO Model RSV-1 Residential to local regulations concerning metering Shut-Off Valve must be performed as system piping with water or after a fire and backflow prevention requirements.
  • Page 7: Limited Warranty

    Information in the domestic piping system. 2. To simulate a sprinkler operation, Products manufactured Tyco Contact your local distributor for avail- open the Alarm Test Connection of Fire Suppression & Building Prod- ability. When placing an order, indi- the fire sprinkler system.
  • Page 8 TFP980 Page 8 of 8 Copyright © 2010 Tyco Fire Suppression & Building Products. All rights reserved.