Individual Specifications - Omron GI-SMD/SID Quick Start Manual

Safety i/o terminal
Table of Contents

Advertisement

GI-SMD/SID

Individual Specifications

GI-SMD1624/GI-SID1224
Model
Number of safety input points
Number of safety output points
Number of test output points
OMRON special safety input device *1
LED indication
Hardware switch setting
Safety input type
Safety input current
Safety input ON voltage
Safety input OFF voltage/OFF current
Safety output type
Safety output rated current
Maximum total safety output current
Safety output ON residual voltage
Safety output OFF residual voltage
Safety output leakage current
Test output type
Test output rated current
Maximum total test output current
Test output ON residual voltage
Test output leakage current
External dimensions *3
Weight
Number of communications that can be set
between NX Units
Power supply voltage
Current consumption *4
Unit power
Inrush current
supplies
Power supply terminal
current carrying capacity *5
Insulation type
Power supply voltage
Current consumption
Output power
Inrush current
supply
Power supply terminal
current carrying capacity *5
Insulation type
Communication connector
External
connection
Screwless clamp terminal
terminal
block
3
GI-SMD1624
12
4
12
Connection unavailable
[V0] LED, [IN] LED x 12, [V1] LED,
[OUT] LED x 4, [MS] LED, [NS] LED,
[PORT LINK] LED x 2
[IP ADDRESS] switch x3 (MODE, x16, x1)
* Factory default
GI-SMD1624 : 192.168.250.2
GI-SID1224 : 192.168.250.3
IEC61131-2 type3
PNP (sinking inputs)
6 mA max.
11 VDC min.
5 VDC max./1 mA max.
Source output (for PNP)
0.5 A max.
2.0 A
1.2 V max.
(between V1 and each output terminal)
2.0 V max.
(between G1 and each output terminal)
0.1 mA max.
Source output (for PNP)
0.7 A max.
5.0 A
1.2 V max. (between V0 and each output terminal)
0.1 mA max.
170 (W) x 65 (H) x 55 (D)
400 g
254 ports max. *3
24 VDC (20.4 to 28.8 VDC)
250 A max.
On cold start at normal temperature
50 A max., 0.1 ms max.
5 A
No insulation: Between unit power supply terminal and internal circuit
24 VDC (20.4 to 28.8 VDC)
50 A max.
On cold start at normal temperature
50 A max., 0.1 ms max.
5 A
Photocoupler insulation
EtherNet/IP communication RJ45 x 2
Top terminal block
Functional earthing
Unit power supply
Input/Test output
Bottom terminal block
Output power supply
Output/Input/Test output
GI-SID1224
---
[V0] LED, [IN] LED x 12,
[V1] LED, [MS] LED, [NS] LED,
[PORT LINK] LED x 2
[IP ADDRESS] Switch= "002"
[IP ADDRESS] Switch= "003"
*2
*2
Top terminal block
Functional earthing
Unit power supply
Input/Test output
Bottom terminal block
Input/Test output

Advertisement

Table of Contents
loading

Table of Contents