QUICK START GUIDE
Step 4A Single Phase - Connect 120/240 Single Phase AC Input Section
Sizing external protectors and wire for all rectifier positions (3 or 6) provides full power for all rectifier positions.
19" 3 rectifier configuration
Rectifier Positions Powered
23" 6 rectifier configuration
Rectifier Positions Powered
Page 7
© 2021 ABB. All rights reserved.
Recommended External Protection and Minimum Wire Size - 6 AWG max.
1
2
3
Recommended External Protection and Minimum Wire Size - 6 AWG max.
1
2
3
4
5
6
120V~ Phase to Neutral
(1200W per rectifier
max)
Maximum
External
Minimum
Rectifiers
Feed
per Feed
Protector
1
20A
2
40A
3
60A
120V~ Phase to Neutral
(1200W per rectifier
max)
Maximum
External
Minimum
Rectifiers
Feed
per Feed
Protector
1
20A
2
40A
3
60A
4
80A
5
100A
6
120A
240V~ Phase to Neutral
(2725W per rectifier max)
Single-Phase Rectifiers
External
Feed
Wire
Protector
14AWG
20A
8AWG
40A
6AWG
60A
240V~ Phase to Neutral
(2725W per rectifier max)
Single-Phase Rectifiers
External
Feed
Wire
Protector
14AWG
20A
8AWG
40A
6AWG
60A
4AWG
80A
2AWG
100A
1AWG
120A
Minimum
Wire
14AWG
8AWG
6AWG
Minimum
Wire
14AWG
8AWG
6AWG
4AWG
2AWG
1AWG