Specifications & Application; Reference Documents - ABB Integritas Quick Start Manual

Table of Contents

Advertisement

QUICK START GUIDE
Specifications and Application
• External Surge Protective Device (SPD) is required on all AC inputs.
• Equipment Safety is Approved in UL1449/IEC 60664-1 Installation Category II environments for ambient
temperature up to 50°C.
Models using IP020ACR125ATEZ rectifiers: For input voltages above 266V, the maximum output current and
power are de-rated by 2.8% per °C for operating ambient above 40°C.
• Equipment and subassembly ports:
1. are suitable for connection to intra-building or unexposed wiring or cabling;
2. can be connected to shielded intra-building cabling grounded at both ends.
• Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an
Integrated Ground Plane (Mesh-Bonding Network or Common Bonding Network).
• Installation Environment - Install where NEC applies.

Reference Documents

These documents are available at
Document
Title
8600092588P
Pulsar XL Product Manual
850049786
Pulsar Plus Controller Family Troubleshooting
0001258890
Integritas Industrial Battery Chargers Ordering Guide