EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Connecting EAGLEHAWK via its RS485-1 Interface to a Panel Bus

NOTE:
When connecting an EAGLEHAWK via its RS485-1 to a Panel Bus I/, it is recommended that the slide switch be set
to "END."
EAGLEHAWK
242526
GND-1
+5V
GND-1
ISO
550 OHM
150 OHM
550 OHM
RS485-1 (+) RS485-1 (-)
END
1 2
F1
24 V
230 V
Fig. 26. Connecting an EAGLEHAWK controller via its RS485-1 interface to a Panel Bus (single transformer)
EAGLEHAWK
242526
GND-1
+5V
GND-1
ISO
550 OHM
150 OHM
550 OHM
RS485-1 (+) RS485-1 (-)
END
1 2
F1
24 V
24 V
230 V
230 V
Fig. 27. Connecting an EAGLEHAWK controller via its RS485-1 interface to a Panel Bus (two transformers)
EN1Z-1005GE51 R0216
CentraLine I/O Module
71
75
Com a
76
72
Com b
73
77
24V~
78
74
24~0
R
T
120 Ohm
CentraLine I/O Module
71
75
Com a
72
76
Com b
73
77
24V~
74
78
24~0
R
T
120 Ohm
F1
CentraLine I/O Module
71
75
Com a
76
72
Com b
73
77
24V~
78
74
24~0
CentraLine I/O Module
71
75
Com a
72
76
Com b
73
77
24V~
74
78
24~0
CentraLine I/O Module
71
75
Com a
72
76
Com b
73
77
24V~
74
78
24~0
CentraLine I/O Module
71
75
Com a
72
76
Com b
73
77
24V~
74
78
24~0
16
CentraLine I/O Module
71
75
Com a
76
72
Com b
73
77
24V~
78
74
24~0
CentraLine I/O Module
71
75
Com a
72
76
Com b
73
77
24V~
74
78
24~0
CentraLine I/O Module
71
75
Com a
72
76
Com b
73
77
24V~
74
78
24~0
CentraLine I/O Module
71
75
Com a
72
76
Com b
73
77
24V~
74
78
24~0