Thermistor Or Related Abnormality (Outdoor Unit) - Daikin Floor Standing Type F-Series Service Manual

Inverter pair
Table of Contents

Advertisement

Troubleshooting

4.20 Thermistor or Related Abnormality (Outdoor Unit)

H9 , J3 , J6 , P4
Remote
Controller
Display
Method of
This fault is identified based on the thermistor input voltage to the microcomputer.
Malfunction
A thermistor fault is identified based on the temperature sensed by each thermistor.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
111
The thermistor input voltage is above 4.96 V or below 0.04 V with the power on.
J3
error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Disconnection of the connector for the thermistor
Defective thermistor
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Defective indoor unit PCB
SiBE06-708_A
Service Diagnosis