Causes For Defects/Remedy - Siemens 7XV5662-0AC02 Manual

Communication converter - copper/synchronous interface
Hide thumbs Also See for 7XV5662-0AC02:
Table of Contents

Advertisement

Available languages

Available languages

5.2

Causes for Defects/Remedy

The following table shows causes for defects during commissioning and potential remedial measures.
No
Signal/Error
.
1
The red Line Activation
LED does not light up.
2
The red Line Activation
LED constantly lights up
3
The yellow Line Trans-
parent LED does not
light up
4
Yellow Data Transfer
LED is not flashing
5
The Line Activation,
Line Transparent, and
Data Transfer LEDs do
not light up
6
The Life Contact relay
does not pick up
Accessories, Communication Converter - Copper/Synchronous Interface, Manual
C53000-B1174-C190-1, Edition 01.2022
Cause
Both CC-CO are in Secondary
Unit Mode.
The line is interrupted.
The line is unsuitable (large
length, large attenuation,
small core cross section).
Both CC-CO are in Main Unit
Mode.
No connection could be
established.
The protection device does
not have a valid payload.
The LEDs are faulty.
The relay is faulty.
Check
Check the jumper position
for the main unit and secon-
dary unit.
Check the loop by bridging
the end of the line.
Check the length, cross-
section, and attenuation.
Check the jumper position
for the main unit and secon-
dary unit.
See no. 1 and 2
Bridge the fiber-optic inter-
face with a fiber-optic cable.
Activate the Test mode with
the protection device
connected.
Press the key, the LEDs must
light up.
Press the key, the relay must
pick up.
Maintenance and Troubleshooting
5.2 Causes for Defects/Remedy
Remedy
Configure a main unit and a
secondary unit.
Replace the power line.
Replace the line.
Configure a main unit and a
secondary unit.
See no. 1 and 2
Send the CC-CO to Siemens.
Replace the fiber-optic cable
or the protection device is
faulty.
Send the CC-CO to Siemens.
Check the line cable or the
protection device is faulty.
33