Monitoring The Test; Checking The Test Results; Cleaning The System - Neutronics QUICK DETECT Operation Manual

A/c sealant detection kit
Table of Contents

Advertisement

Warranty
3.4

Monitoring the Test

Observe flow meter reading for 3 minutes. Note that during the initial 30-60 seconds the flow rate
may rise due to water being pushed through the sensing plug. Note the highest reading obt
during the initial 60-seconds and compare to the reading obtained at the end of 3-minutes.
At the end of the 3-minute period, disconnect the
3.5

Checking the Test Results

If the flow drops 30% or more from the initial, stabilized rea
remains within 30%, sealant is NOT present.
Eg. Initial flow = 4.5, Final Flow = 2.5 Sealant is present.
Initial Flow = 4.5, Final Flow = 4.0 Seala
3.6

Cleaning the System

After completion of the test, remove the flow meter from the system and allow any residual oil to
drain from the hose assembly.
Manual Part Number:
5-06-7000-62-0
test rig from the A/C system high side port.
nt is NOT present.
Manual File:
MN-A-0001 Rev. E
ding, then sealant is present. If the flow
Revision Date: June 5, 2006
ained
Page 3-6

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QUICK DETECT and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

7-08-1000-51-0

Table of Contents