Warranty
3.4
Monitoring the Test
Observe flow meter reading for 3 minutes. Note that during the initial 30-60 seconds the flow rate
may rise due to water being pushed through the sensing plug. Note the highest reading obt
during the initial 60-seconds and compare to the reading obtained at the end of 3-minutes.
At the end of the 3-minute period, disconnect the
3.5
Checking the Test Results
If the flow drops 30% or more from the initial, stabilized rea
remains within 30%, sealant is NOT present.
Eg. Initial flow = 4.5, Final Flow = 2.5 Sealant is present.
Initial Flow = 4.5, Final Flow = 4.0 Seala
3.6
Cleaning the System
After completion of the test, remove the flow meter from the system and allow any residual oil to
drain from the hose assembly.
Manual Part Number:
5-06-7000-62-0
test rig from the A/C system high side port.
nt is NOT present.
Manual File:
MN-A-0001 Rev. E
ding, then sealant is present. If the flow
Revision Date: June 5, 2006