<ENTER>=Accept
Prg: [LED]
2.
Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the
LED point you want to edit. The display appears similar
to the following.
LED Card 5, Pt 1
LED
3.
Press <ENTER>. The next prompt appears similar to
the following:
LED Card 5, Pt 1
Fn: [Edit Mode]
4.
Press <ENTER>. A prompt similar to the following
appears.
Mode Prg - Output
[TRBL]
5.
Use the <NEXT> and <PREV> keys to scroll through
the available modes. As you scroll through the modes,
the default reference address for the mode appears to the
right of the mode. Refer to Table 6-3 for a list of the
available modes.
6.
When the appropriate mode is selected, use the right
arrow key to move the cursor brackets over to the refer-
ence point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a
text-based description. Refer to Table 6-4 for a list of
common reference points. For example:
Type: BZONE
IDC10
7.
Use the <NEXT> and <PREV> keys to scroll through
the list of available reference points.
8.
Press <ENTER> when the appropriate reference point is
displayed. The prompt shown in Step 4 reappears.
9.
Press <ENTER>. A prompt appears, asking you to con-
firm the changes.
10. Press <ENTER> to confirm the changes.
Mode
FIRE
Technical Manuals Online! - http://www.tech-man.com
1/24
15-10
Fire
Table 6-3 LED Modes
Description
Output activates when referenced
point is in an Alarm condition.
firealarmresources.com
Chapter 6. Manually Programming Annunciators
Table 6-3 LED Modes
Mode
Output activates when referenced
SUPV
point is in a Supervisory condition.
Output activates when referenced
TRBL
point is in a Trouble condition.
Output activates when the refer-
DISA
enced point is Disabled.
Output activates when the state of the
ON
reference point is ON.
Output activates when the state of the
OFF
reference point is OFF.
Output activates when any point is in an
LF
alarm condition.
Output activates when any point is in a
LS
supervisory condition.
Output activates when any point is in a
LT
trouble condition.
Table 6-4 Common LED Reference Points
Reference
Point
Separate reference point for each
IDNet initiating device. State moni-
IDNet 1-200
tored determined by selected LED
mode.
Aux Relays 1
Separate reference point for each
and 2
relay. State monitored determined
by selected LED mode.
City/DACT
Separate reference point (18-14) for dis-
Disconnect
connect and trouble. Typical use is to
monitor the ON state of either point.
City Trouble
Control
Bypass
Separate reference point for each type
Elevator
of bypass.Typical use is to monitor the
Bypass
ON state of any of the points.
Door Bypass
6-5
Description
Description