Chapter 3. Auto-Programming
Table 3-2 Default Function Type Assignments,
IDNet Devices, NACs, and Relays (Cont'd)
Function
Device
Type
SIGNAL
OTS
ISOL
ISOL
SIG1-2
OTS
SIG3-4
OTR
AUX1
OTR
AUX2
TRBL
NAC, Relay, and Signal Circuit Output Mode
Assignments
Table 3-3 lists the default output mode (steady, temporal,
etc.) assignments for the NAC, Relay, and Signal circuits.
The output mode is a programmable attribute and it can be
manually changed, as described in Chapter 5 of this manual.
Table 3-3 Default NAC, Relay, Signal Circuit Output
Circuit
SIG1-2 (NAC)
SIG3-4 (NAC
AUX1 & AUX2
RELAY Modules
SIGNAL Mod-
ules
Annunciator Defaults
Annunciator cards found during the Auto-Program process
are added into the default configuration.
•
LCD Annunciators are configured to receive all events.
Refer to Chapter 6 for information on manually pro-
gramming which events are received by the LCD
Annunciator.
•
LED Annunciators and 24-I/O modules are not pro-
grammed for default operation.
DACT Defaults
The defaults for the DACT are listed below. Refer to Chap-
ter 5for information on manually programming the DACT.
Technical Manuals Online! - http://www.tech-man.com
Description
General Alarm Signal (on-til-silence)
IDNet loop isolator
General Alarm Signal (on-til-silence)
General Alarm Signal (on-til-reset)
General Alarm Relay (on-til-reset)
Trouble Relay (on-til-clear)
Mode Assignments
Default Output Method
Temporal Code A three pulse coding pattern
consisting of three ½ second pulses, each sep-
arated by ½ second silence. Each group of
three pulses is separated by 1.5 seconds of
silence.
Synchronized. Used with visual NACs. Pro-
grams all visuals to flash simultaneously.
Steady on
Steady on
Steady on
firealarmresources.com
•
Tone else pulse dialing
•
AC Fail reporting delay is 6 hours
•
Reporting format is CID
•
Primary and Secondary Phone Number. There are no
values for the primary and secondary phone numbers or
account codes.
•
The CID Group and CID Point Identifier default to the
IDNet device address.
•
Default event codes are shown in Table 3-4.
Table 3-4 Default CID Event Codes
Function Type
Fire
FIRE
110
WATER
113
HEAT
114
DUCT
116
PULL
115
SMOKE
111
SO
-
WSO
110
SUPV
-
UTIL
-
TROUBLE
-
VSMOKE
111
LATSUPV
-
STYLEC
110
OTHER TRBL*
-
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
3-4
Supervisory
Trouble
-
330
-
330
-
330
-
330
-
330
-
330
200
330
200
330
200
330
-
330
-
330
-
330
200
330
-
330
-
330