Table 4-1 Hardware Types for Sensors/Bases
Sensor
Models
4098-9714
4098-
9714C
Photo-
Electric
Smoke
Detector
Sensor
4098-9733
4098-
9733C
Heat
Detector
Sensor
Technical Manuals Online! - http://www.tech-man.com
Base
Models
4098-9755
4098-9755C
Two-wire duct base w/o relay
4098-9792
4098-9792C
Detector base w/o remote LED
4098-9789
4098-9789C
Detector base with remote LED
4098-9756
4098-9756C
Four-wire duct base with relay
4098-9791
4098-9791C
Detector base with relay
4098-9793
4098-9793C
Isolator base
4098-9794
4098-9794C
Sounder base
See Note1 below
4098-9792
4098-9792C
Detector base w/o remote LED
4098-9789
4098-9789C
Detector base with remote LED
4098-9791
4098-9791C
Detector base with relay
4098-9793
4098-9793C
Isolator base
4098-9794
4098-9794C
Sounder base
See Note 1 below.
firealarmresources.com
Chapter 4. Manually Programming IDNet Points
Table 4-1 Hardware Types for Sensors/Bases
Sensor
Use this
Models
Hardware
Type
4098-9754
4098-
9754C
Combina-
tion Photo
PHOTO
Electric
Smoke
Detector
and Heat
Detector
Note 1.
The operation of sounder bases is controlled by
RPHOTO
the Single Station system option. See Chapter 7
of this manual for additional information.
Note 2.
A multi-detector base, coupled with a combina-
RPHOTO
tion photo/heat sensor, uses two addresses. Make
sure to set the address on the base to an even
number, and do not set any other device to the
IPHOTO
address that you set plus one. The even number
represents the Photo portion of the combination
sensor. The address plus one represents the heat
SPHOTO
portion of the sensor.
Note 3.
The HEAT, RHEAT, IHEAT, and SHEAT func-
tion types set the heat detector to a fixed sensitiv-
ity of 135°F. An alarm is initiated when the
HEAT
temperature rises beyond this temperature.
OHEAT
The OHEAT, ROHEAT, IOHEAT, and SOHEAT
function types set the heat detector for rate-of-rise
RHEAT
operation. With this hardware type, if the temper-
ROHEAT
ature rises beyond 135°F or if the temperature
rises at a rate of 15°F per minute, an alarm is ini-
IHEAT
tiated.
IOHEAT
Table 4-2 Hardware Types, IDNet Modules
SHEAT
SOHEAT
Zone Individual Addressable Module (IAM) for
Class A or B Signal Circuits
Supervised Individual Addressable Module (IAM)
Indiv. Addressable Module with Relay
4-3
Base
Models
4098-9795
4098-9795C
Multi-detector sounder base
See Note 1 and Note 2 below.
4098-9796
4098-9796C
Multi-detector base with LED
See Note 2 below.
Module
4090-9007
4090-9001
4090-9002
Use this
Hardware
Type
SPHOTO &
SHEAT
PHOTO &
HEAT
Use this
Hardware
Type