Chapter 5. Manually Programming NACs, Relays, and DACT
Note: You can also use the special characters B, C, D, and E
when specifying the Secondary Phone Number. See the
description of these characters in the section "Setting Pri-
mary Phone Number" above.
<ENTER>=Accept
Opt: [Sec Phone #]
1.
Press <ENTER>. The following prompt appears.
Sec Phone #
[X] XXXXXXXXXXXXXXXX
2.
Use the arrow keys to move the cursor from one digit to
another. Use the keypad numbers, or use the NEXT and
PREV keys to enter each number. Press <ENTER>
when the number is correctly entered. A prompt appears
asking you to confirm the number that you entered.
3.
Press <ENTER> again. The prompt shown above Step 1
reappears.
4.
Press the <NEXT> key. The prompt for the Secondary
Account Number appears.
Setting Secondary Account Number
The secondary account number is a unique identifier
assigned and used by the supervising station.
Sec Account #
[0] 000
1.
Use the arrow keys to move the cursor from one number
to another. Use the NEXT and PREV keys or the key-
pad to enter each number.
2.
Press <ENTER> when the number is correctly entered.
A prompt appears asking you to confirm the number
that you entered.
3.
Press <ENTER>. The prompt shown above Step 1 reap-
pears.
4.
Press the <NEXT> key. The prompt for setting the dial-
ing mode appears.
Setting Dialing Mode
The dialing mode specifies the type of phone line being used
by the DACT.
<ENTER> = Accept
Dialing Mode
1.
Press <ENTER>.
Dialing Mode
[Tone else Pulse]
Technical Manuals Online! - http://www.tech-man.com
2.
3.
4.
5.
Setting Pulse Rate
The Pulse Rate option specifies the pulse rate used with
either the 3/1 or 4/2 pulse format. This option does not apply
to other formats.
1.
2.
3.
4.
5.
Setting Pulse Frequency
The pulse frequency specifies the frequency (in KHz) of the
pulses used by the DACT.
1.
2.
5-8
firealarmresources.com
Use the NEXT and PREV keys to move from one
choice to another. Choices are tone (touchtone), pulse,
and tone else pulse (attempt to dial with a touchtone for-
mat and if that fails, use a pulse format).
Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
Press <ENTER>. The prompt shown above Step 1 reap-
pears.
Press the <NEXT> key. The prompt for the Pulse Rate
appears.
<ENTER> = Accept
Pulse Rate
Press <ENTER>.
Pulse Rate
[20 PPS]
Use the NEXT and PREV keys to move from one
choice to another. Choices are 20 pulses per second
(PPS), which is the default, and 10 PPS.
Press <ENTER> to accept the choice. A prompt appears
asking you to confirm the choice.
Press <ENTER>. The prompt shown above Step 1 reap-
pears.
Press the <NEXT> key. The prompt for the Pulse Fre-
quency appears.
<ENTER> = Accept
Opt: [Pulse Freq]
Press <ENTER>.
Pulse Freq
[1.9KHz Data]
Use the NEXT and PREV keys to move from one
choice to another. Choices are
1.9 KHz
1.8 KHz