Field Programming
CHAPTER 2
The FIRE•COMMAND•25/50 VECP can be field programmed using option DIP switches S1 and S5 located in the
upper right side of the main circuit board. It is recommended that tone selection, message repeat cycles and back-
ground music options be reviewed and approved by the local AHJ. Refer to the following illustration for details on
DIP switch placement in the ON and OFF positions.
FIGURE 2-1:
2.1

S1 DIP Switch Settings

Switch 1 - Temporal pattern generated per ANSI S3.41 when Switch 1 is ON and Switches 2 and 3 are OFF
Switches 2 and 3 - used to determine what tone will be transmitted over the speakers before and after the mes-
sage is transmitted as well as the backup tone to be transmitted if the digital voice generator fails.
TABLE 2-1:
SWITCH
2
OFF
OFF
ON
ON
Switch 4 - used to determine if the tone selected by S1 switches 2 and 3 will be generated before the message
is transmitted:
Technical Manuals Online! - http://www.tech-man.com
Field Programming
Field Programming DIP Switches
OFF = No temporal pattern - tone generated as selected by Switches 2 and 3 (factory default setting).
ON = Temporal pattern generated on steady tone. Switches 2 and 3 must be in the OFF position.
Switch Settings for Tones
SWITCH
TONE TRANSMITTED BEFORE AND
3
AFTER DIGITAL VOICE MESSAGE
OFF
STEADY
ON
SLOW WHOOP (factory default)
OFF
ON
CHIME
OFF = No tone before message
ON = Tone before message (factory default setting)
firealarmresources.com
Hi-Lo
Document #50580
Rev. C
8/12/97
P/N 50580:C
15