S5 DIP Switch Settings

Switch 5 - used to determine if the tone selected by S1 switches 2 and 3 will be generated after the message is
transmitted:
OFF = No tone after message
ON = Tone after message (factory default setting)
Switch 6, 7 and 8 - used to determine the number of times the voice message will repeat.
Switch Settings for Message Repeat
TABLE 2-2:
SWITCH
SWITCH
6
OFF
ON
OFF
ON
OFF
ON
1. Some jurisdictions require tone evacuate only. This option prevents voice messages
from being generated. Verify with local AHJ if voice message is allowed and the num-
ber of times the message may be repeated.
2.2
S5 DIP Switch Settings
Switch 1 - Future use
Switch 2 - Provides two distinct functions for message recording and speaker circuit selection as follows:
Message Recordings:
When recording a message to be played back by the Digital Message Generator, Switch 2 is used to
set the number of messages to be recorded:
OFF = one 60 second 'fire' message (factory default setting).
Note: Can also be recorded as one evacuate message in two languages; one language recorded imme-
diately after the first language.
ON = two 30 second messages.
Note: Both messages can be 'fire' related or one may be 'nonfire' related, i.e. 'fire evacuation' and 'fire
clear' messages or 'fire' and 'tornado warning' messages.
Speaker/Message Selection
During panel operation, Switch 2 is also used to determine which speaker circuit(s) will be activated
by Command Input Circuits 1 & 2 and which message will be transmitted. In order for the speaker
circuit select function to operate, be certain to install the second amplifier and do not select the backup
feature.
16
Technical Manuals Online! - http://www.tech-man.com
SWITCH
NUMBER OF TIMES TO REPEAT DIGITAL
7
8
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
INFINITE (until FACP NAC or Manual Evacuate
ON
ON
firealarmresources.com
VOICE MESSAGE
1
Tone only, no voice
3
4
6 (factory default)
8
switch is reset)
Document #50580
Rev.C
8/12/97
P/N 50580:C