Section Three: Mounting

Screw
LCD-40 Preparation
The LCD-40 can be surface or semi-flush
mounted ONLY in a three-gang electrical box,
Fire•Lite P/N 10103 or equivalent, with a
minimum depth of 2.125". The LCD-40 cannot
be mounted in three gangable electrical switch
boxes connected together. Select and remove
the appropriate knockout(s), pull the necessary
wires through the knockouts and mount the
three-gang box in or on the wall depending on
the type of installation desired. Be certain that
power is not applied to the wiring during the
installation procedure.
Screw
Note: To ensure static protection, all enclosures, including the LCD-40 electrical box,
must be connected to earth ground! Never use the shield for grounding purposes.
To mount the LCD-40 in the electrical box, the trim ring must first be removed. The trim
ring is held in place by two screws inserted through the top and bottom edge as illus-
trated. Removal of the trim ring will expose a metal flange with mounting holes.
LCD-40 flange
LCD-40 Trim ring
Figure 3-1: LCD-40 Hardware