24 VDC TB4
Terms 3 (+)
and 4 (-)
DIM-485
MS-9200 in grounded box
Top
CAUTION! Please be certain to secure the DIM-485 module to the MS-9200 and to keep all wiring
from mechanically interfering with the DIM-485.
Note:
1) Ferrite Core P/N 29090 is required to meet FCC Part 15 requirements if the EIA-485 wiring is not
in conduit. Twisted, shielded wire is recommended for the EIA-485 communications loop.
2) Six conductor overall shielded wire may be used for the four EIA-485 wires and the two power
wires. It is, however, strongly recommended that the power and communication wires be
separate whenever possible.
16
Technical Manuals Online! - http://www.tech-man.com
EIA-485
1
2
3
4
Figure 4-4: Wiring FACP to LCD-40
Document 50327
firealarmresources.com
LCD-40 in grounded box
Ferrite Core P/N
29090 Required
LCD-40 in grounded box
Ferrite Core P/N
29090 Required
P1
(+) EIA-485
IN
(-) EIA-485
(+)
(-)
EIA-485
OUT
(+) 24 VDC
IN
(-) 24 VDC
Rev B
3/16/96
P/N 50327:B
P2
Earth
Ground -
Optional
Shield
n/c
Connect
(+)
(-)
24 VDC
OUT