Mounting

LCD-40 Series Annunciator Preparation

Mounting
Section 3:
3.1
LCD-40 Series Annunciator Preparation
The LCD-40 Series Annunciators can be surface mounted in a three-
gang electrical box such as the P/N SBB-3 (2.75" depth) or semi-flush
mounted in a three-gang electrical box, P/N 10103 or equivalent, with a
minimum depth of 2 3/16". The LCD-40 Series Annunciators cannot be
mounted in three gangable electrical switch boxes connected together.
Select and remove the appropriate knockout(s), pull the necessary wires
through the knockouts and mount the three-gang box in or on the wall
depending on the type of installation desired. Be certain that power is
not applied to the wiring during the installation procedure.
Note: To ensure static protection, all enclosures, including the LCD-40
Series electrical box, must be connected to earth ground! Never use the
shield for grounding purposes.
To mount the LCD-40 Series Annunciators in an electrical box, the trim
ring must first be removed. The trim ring is held in place by two screws
inserted through the top and bottom edge as illustrated in Figure 3-1.
Removal of the trim ring will expose a metal flange with mounting
holes. Refer to "Hardware and Backboxes" on page 16.
Figure 3-1: Trim Ring Removal
Screw
Screw
15
Document 50327
Rev D1 1/14/99 P/N 50327:D1
Technical Manuals Online! - http://www.tech-man.com