Valid entries are 0 - F with the numeric digits as dialed numbers and hex
digits indicating the following:
A= * on a Touchtone phone keypad
B= # on a Touchtone phone keypad
C= look for secondary dial tone for up to 2 seconds (then, dial anyway)
D= 3-second pause
E= 5-second pause
F= end of phone number
Programming Primary Number Communication Format. (16)
One location is needed to select the Communication Format to the
primary phone number. Address 16 is used for this purpose. The default
(factory setting) for this address is A
1800 Hz "Carrier", 2300 Hz "ack." You may enter 2 through D in place
of the default, then hit
[ENTER/STORE].
following:
0: Not Used
1: Not Used
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-1
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-1
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-1
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK--- Table 4.3-1
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-1
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-1
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-1
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-1
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-2
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK - Table 4.3-1
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK -- Table 4.3-2
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-1
E: Not Used
F: Not Used
Note: Consult your Central Station for proper selection or consult our factory
representatives. For any format chosen, the MS-5012 automatically programs
all of the event codes. See the following tables.
15465 Rev F
firealarmresources.com
16 A
, which is 4+2 Standard,
Zero through F represents the
5/2/97 P/N 15465:F