Fire-Lite Alarms MS-5012 Installation, Operation, And Programming Manual page 37

Control communicator
Table of Contents

Advertisement

4.2 Switch
Functions
4.3 Programming
Technical Manuals Online! - http://www.tech-man.com
When in Programming Mode, the trouble light will be on, the trouble
relay driver will be activated, but the communicator will not be
activated to report this trouble. Transmissions started before entering
program mode will continue during programming.
The first three locations from the left represent the memory address
which can go from 00 up to 243 (Alpha characters are not used). The
last location (farthest right) represents the contents of the memory
address. The first address displayed is shown below:
The Function of each switch is shown below:
No function in this mode
u v w
123f q'
These keys can
{
456e r
be used for
address entry
789d s=
and/or data
entry
a0bc t
Programming the Primary phone number. (00-15)
Sixteen addresses are set aside with "F" being the factory default.
(from
If your phone # is 484-7161, type
the display will read
t
press
the next address
Enter the remaining numbers in their respective addresses:
4 8 4 7 1 6 1 F F F F F F F F F
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 .
15465 Rev F
5/2/97 P/N 15465:F
firealarmresources.com
00 F
address data
00 F
15 F
to
00 4
to save and bring you to
01 F
- Select operating mode
- Increment memory address
- Decrement memory address
- Once = First memory address
Twice = type any address
- Save data, go to next address
).
4
,
,
.
37