Switch Functions For Lcd-40 Only; Key-Switch; Acknowledge - Fire-Lite Alarms LCD-40 Series Manual

Remote fire annunciator for use with ms-9200(c)/e addressable fire alarm control panel
Hide thumbs Also See for LCD-40 Series:
Table of Contents

Advertisement

Operation
2.2

2.2.1 Key-switch

The key-switch is used to enable
and disable the operation of the
function switches if switch 2 on
DIP switch SW1 has been placed
to the On (Down) position.
To enable the Acknowledge,
Silence, Drill and Reset function
switches, insert a standard
Fire•Lite key into the key-switch
located at the top right corner of
the LCD-40. Make certain the
key is inserted completely before
attempting to turn it. Turn the key
clockwise until it stops. Leave the key inserted while pressing the
function switches. When finished with the function switches, turn
key-switch counterclockwise to disable function switches.
Note that the key-switch should normally be in the disabled position
(fully counterclockwise), with the key removed and access to the key
restricted to authorized personnel only. Do not leave the key unat-
tended in the LCD-40.

2.2.2 Acknowledge

When the Acknowledge switch is pressed and released, the LCD-40
sends an Acknowledge command to the control panel. Pressing the
Acknowledge switch silences the local piezo sounder, the sounders
located in all other system annunciators and the sounder located on
the Fire Alarm Control Panel's main circuit board. It will also
change all flashing system LEDs to steady on. Only one press is
necessary regardless of the number of new alarms, troubles or super-
visory signals.
An acknowledge message is also sent to the printer and the history
files in the MS-9200. Multiple active events (alarms, troubles,
supervisories) are scrolled on the display at a one second rate, but
may be held for sequential display by pressing and holding the
Acknowledge switch.
When more than one event exists, the first press of the Acknowledge
switch silences system piezo sounders and changes all flashing
12
Technical Manuals Online! - http://www.tech-man.com

Switch Functions for LCD-40 Only

Document 50327
Rev D1 1/14/99 P/N 50327:D1
firealarmresources.com
Switch Functions for LCD-40 Only
Key-switch (shown in Off position)