Omron H7BR Series Manual page 6

Hide thumbs Also See for H7BR Series:
Table of Contents

Advertisement

H7BR
STANDARD COUNTER OUTPUT OPERATIONS
H7BR-B
(Bold line represents present value; Output 2 operation applies for single-preset models.)
Output Mode N Present value display and outputs are maintained until reset.
Up
Reset
999,999
Preset 2
Preset 1
0
Output 1
Output 2
Output Mode F Present value runs continuously. Outputs are maintained until reset.
Up
Reset
999,999
Preset 2
Preset 1
0
Output 1
Output 2
Output Mode C Present value is placed in reset start status as soon as preset count is reached; the preset is not actually displayed.
Outputs are one-shot and operate repeatedly. Output 1 latches ON, and goes OFF after expiration of the one-shot period for Output 2.
One-shot time periods for Output 1 and 2 are independent.
Up
Reset
999,999
Preset 2
Preset 1
0
Output 1
Output 2
One-shot output from Output 1
Sustained output
One-shot outputs can be set to 10, 50, 100, 200, 500 or 1,000 ms.
Down
Down
Down
One-shot output from Output 2
Sustained output
6
H7BR
Reversible A, B, and C
Reversible A, B, and C
Reversible A, B, and C