H7BR
+/- Range Counter Output Operation (Continued)
H7BR-C
(Bold line represents present value; Output 2 operation applies for single preset models.)
Output Mode H Present value increments and decrements within the display's range. Output 1 is ON whenever present value is
greater than or equal to preset 1; Output 2 is ON whenever present value is greater than or equal to preset 2.
Comp.
Reset
999,999
Comp.
Preset 2
Preset 1
0
-999,999
Output 1
Output 2
One-shot output
One-shot outputs can be set to 10, 50, 100, 200, 500 or
1,000 ms.
Instantaneous (equals) output
Notes
Counting inputs are not acknowledged while the reset input is
ON.
The compensation input is valid only when the present value is
being incremented.
BATCH COUNTER OPERATION (H7BR-B models)
The bold line indicates the batch count.
The batch counter counts the number of times the preset is reached for single preset models, and the number of times preset 2 is
reached for double preset models.
Batch output remains ON and runs continuously until reset.
Batch count reset
Batch count preset
0
Batch output
Notes
The batch count will remain zero while the reset input is ON.
Batches are counted, but no batch outputs are made when the
batch preset is set to zero. The batch count will return to zero if
999,999 is exceeded.
The batch count and the batch output is not reset by any method
other than the batch count reset (i.e., it is not affected by the reset
key or by other reset inputs).
Reversible A, B, and C
Edge input
Sustained output/level input
One-shot outputs, when ON, are turned OFF when the reset
input goes ON, but are left ON for the one-shot time period
when the compensation inputs goes ON. One-shot outputs,
when ON, are reset and the one-shot output is restarted if a
preset designating the output is reached.
If the batch output is ON when power is interrupted, it will go
ON when power is restored.
The batch output will be turned ON if the batch preset is
changed from a value greater than the present batch count to a
value less than the present batch count.
The batch output will remain ON if the batch preset is changed
from a value less than the present batch count to a value
greater than the present batch count.
10