3. Basic Specification

Functions of OIS

The function of the OIS is registered with the OIS-DS engineering tool.
The basic specification of OIS is shown in Table 3.1.
Item
Display
Input Device
Security
Alarm Monitoring Group
Screen Configuration
Alarm Window
Auto Screen Display
Alarm Confirmation Method
Alarm Grade
Signal Category
Service Name
Historical Trend Screen
Realtime Trend Marks
Table 3.1.
Basic Specification of OIS functions
Specifications
(1280 × 1024) (1024 × 768)
Mouse and touch panel(optional)
Dedicated operator controller(optional)
Engineer controller(optional)
User management by NT's logon
16 users/system
64 signal categories
64 stations/alarm monitoring group
System display area : 1
Operator window area: Max.4 partitions
(However, it is one partition at the time of
1024 × 768 dots.)
Auto window display
Yes
Process alarm : Selected from Type A/B/C
(for each tag)
System alarm : Type B
Process alarm : 4 levels
(Major,Medium,Minor,Warning)
System alarm : 3 levels (Major,Minor,Warning)
Guidance
: 4 levels
(Major,Medium,Minor,Message)
Process alarm : for each tag
: for each tag - specific alarm
64 signal categories/system
Tag number character : ANK 16 characters
Tag name
: ANK 32 characters
Signal category name : ANK 16 characters
Status name
: ANK 16 characters
Station name
: ANK 32 characters
Industrial unit
: ANK 16 characters
Tagging character
: ANK 16 characters
Guidance
: ANK 40 characters
Guidance details
: ANK 512 characters
Trend group name
: ANK 30 characters
8 pens/group
Max.1024 screens/system
1024 points
3. Basic Specification