Start and shut down the inverter
Before turning the inverter on, please make sure the PV/Battery input voltage and
current are within the MPPT limits.
Follow the steps below to turn the inverter on:
1.Pull the PV/Battery and AC cable make sure there is no loose or shaking.
2.Make sure the cable polarity is correct and voltage is less than 1100V
3.Switch on the build-in DC isolator at the bottom of the inverter.
4.Switch on the PV/Battery Array and DC isolator next to your inverter, if you can not
find this switch, skip this step.
5.Switch on the Solar AC isolator if the inverter is more than 3 meters away from your
switchboard.
6.Switch on the solar supply main switch in the switch board.
12.2 Shut down the inverter
Don't disconnect the DC connector while the inverter is connected to
the grid.
Danger
Steps to turn off the inverter:
1. Disconnect the AC circuit breaker to prevent the inverter from starting again;
2. Turn off the DC switch;
3. Turn off the BAT input switch of the BAT;
4. Check the operating status of the inverter;
5. Wait until the LED and OLED display are off, indicating that the inverter is turned off.
39

Troubleshooting

13.1 Error message
When a malfunction occurs, an error message will be displayed on the OLED screen
and the LED indicator red will light up. Faults include system faults and inverter faults.
In some cases, you may be advised to contact Growatt, please provide the following
information.
Information about the inverter::
●Serial number
●Model
●Error message on OLED
●A short description of the problem
●Grid voltage
●DC input voltage
●Can you reproduce the failure? If so, how?
●Has this problem occurred in the past?
●What were the environmental conditions when the problem occurred?
Information about photovoltaic panels:
●PV panel manufacturer's name and model
●Panel output power
●Voc of the panel
●Vmp of the panel
●Imp of the panel
●The number of panels in each string
●If you need to replace the device, please ship it to the original box.
13.2 System error
Warning Code
Warning
Description
message
1.After shutdown,Check the panel is normal.
Warning 200 String fault
2 . I f e r r o r m e s s a g e s t i l l e x i s t s , c o n t a c t
manufacturer.
S t r i n g P I D q u i c k
1.After shutdown,Check the string terminal wiring.
Warning 201
c o n n e c t t e r m i n a l
2.If the error message still exists, contact the
detection error
manufacturer.
DC SPD function
1.After shutdown,Check the DC SPD.
Warning 202
abnormal
2.If error message still exists,contact manufacturer.
1.Check the PV1 or PV2 wiring is short-circuited
Warning 203 PV Circuit short
2.If error message still exists,contact manufacturer.
1.After shutdown,Check the dry Dry contact wiring.
Dry contact
function
Warning 204
2.If the error message still exists, contact
abnormal
manufacturer.
1.Restart inverter.
Warning 205 PV Boost driver broken
2.If error message still exists,contact manufacturer.
AC SPD function
1.After shutdown,Check the AC SPD.
Warning 206
abnormal
2.If error message still exists,contact manufacturer.