5

Installation

5.1 Basic installation requirements
Ø
The wall on which the inverter is mounted must be sturdy and can withstand the
weight of the inverter for a long time (refer to the specifications in Chapter 17 for the
weight of the inverter);
Ø
The installation location must match the size of the inverter;
Ø
Do not install the inverter on a building constructed of flammable or heat-resistant
materials;
Install the inverter in an eye-view orientation to facilitate inspection of the OLED
Ø
display and maintenance work;
The machine's degree of protection is IP66 and can be installed indoors and
Ø
outdoors;
It is not recommended to expose the inverter directly to strong sunlight to prevent
Ø
overheating and cause power derating;
The humidity of the installation environment should be between 0 and 90%;
Ø
The ambient temperature around the inverter should be between -25 ° C ~ 60 ° C;
Ø
Ø
The inverter can be mounted on a plane that is tilted vertically or backwards.
Fig 5 1 Installation diagram
.
Ø
In order to ensure the normal operation of the machine and the convenience of
personnel operation, please pay attention to provide sufficient clearance for the
inverter. Please refer to the figure below:
Direction
Above
Under
Both sides
Forward
11
Minimum clearance (mm)
500
500
300
300
Fig 5.2 Installation dimensions for one inverter
Fig 5.3 Installation dimensions for multiple inverters
Ø
Do not install the inverter on the TV antenna, other antennas or antenna cables;
Ø
Do not install the inverter in the living area;
Ø
Do not install the inverter where children can reach it;
Ø
The inverter should be installed in a sheltered and protected location such as
cool, rain-proof;