Application guidelines

6.5 Setting up the energy metering

6.5.1 Produced heat

6.5.2 Consumed energy

Installer reference guide
54
If the applicable legislation requires a higher temperature than the maximum
tank setpoint during disinfection (see [2-03] in the field settings table), you can
connect a DHW pump and heater element as shown above.
If applicable legislation requires disinfection of the water piping until the tapping
point, you can connect a DHW pump and heater element (if needed) as shown
above.
Configuration
The indoor unit can control DHW pump operation. For more information, see
4
"11 Configuration" [
 141].
Via the user interface, you can read out the following energy data:
-

Produced heat

-

Consumed energy

You can read out the energy data:
-
For space heating
-
For space cooling
-
For domestic hot water production
You can read out the energy data:
-
Per month
-
Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.
INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
The produced heat is calculated internally based on:
-
The leaving and entering water temperature
-
The flow rate
Setup and configuration: No additional equipment needed.
You can use the following methods to determine the consumed energy:
Calculating
Measuring
ERLA11~16DAV3+W1 + EBVH/X11+16S18+23DJ
Daikin Altherma 3 R F
4P643602-1 – 2021.09