2-Points Curve - Daikin Altherma 3 R F Installer's Reference Manual

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

11.5.2 2-points curve

ERLA11~16DAV3+W1 + EBVH/X11+16S18+23DJ
Daikin Altherma 3 R F
4P643602-1 – 2021.09
Types of weather-dependent curve
There are 2 types of weather-dependent curves:

2-points curve

Slope-offset curve
Which type of curve you use to make adjustments, depends on your personal
preference. See
"11.5.4 Using weather-dependent
Availability
The weather-dependent curve is available for:
Main zone - Heating
Main zone - Cooling
Additional zone - Heating
Additional zone - Cooling
Tank (only available to installers)
INFORMATION
To operate weather dependent, correctly configure the setpoint of the main zone,
additional zone or tank. See
Define the weather-dependent curve with these two setpoints:
Setpoint (X1, Y2)
Setpoint (X2, Y1)
Example
Y2
Y1
X1
curves" [
"11.5.4 Using weather-dependent
a
X2
11
Configuration
|
4
 165].
curves" [
4
 165].
Installer reference guide
163

Advertisement

Table of Contents
loading

Table of Contents