Field settings table
Breadcrumb Field code
Setting name
9.I
[9-08]
What is the maximum desired LWT for add. zone in cooling?
9.I
[9-09]
What is the allowed undershoot in cooling?
9.I
[9-0A]
What is the room buffering temperature in heating?
9.I
[9-0B]
What is the room buffering temperature in Cooling?
9.I
[9-0C]
Room temperature hysteresis.
9.I
[9-0D]
Pump speed limitation
9.I
[9-0E]
--
9.I
[C-00]
Domestic heating water priority.
9.I
[C-01]
--
9.I
[C-02]
Is an external backup heat source connected?
9.I
[C-03]
Bivalent activation temperature.
9.I
[C-04]
Bivalent hysteresis temperature.
9.I
[C-05]
What is the thermo request contact type for the main zone?
9.I
[C-06]
What is the thermo request contact type for the add. zone?
9.I
[C-07]
What is the unit control method in space operation?
9.I
[C-08]
Which type of external sensor is installed?
9.I
[C-09]
What is the required alarm output contact type?
9.I
[C-0A]
--
9.I
[C-0B]
--
9.I
[C-0C]
--
9.I
[C-0D]
--
9.I
[C-0E]
--
9.I
[D-00]
Which heaters are permitted if prefer. kWh rate PS is cut?
9.I
[D-01]
Contact type of preferential kWh rate PS installation?
9.I
[D-02]
Which type of DHW pump is installed?
9.I
[D-03]
Leaving water temperature compensation around 0°C.
9.I
[D-04]
Is a demand PCB connected?
9.I
[D-05]
Is the pump allowed to run if prefer. kWh rate PS is cut?
9.I
[D-07]
Is a solar kit connected?
9.I
[D-08]
Is an external kWh meter used for power measurement?
9.I
[D-09]
Is an external kWh meter used for power measurement, kWh meter used for smart
grid or a gas meter for hybrid unit?
9.I
[D-0A]
--
9.I
[D-0B]
--
9.I
[D-0C]
--
9.I
[D-0D]
--
9.I
[D-0E]
--
9.I
[E-00]
Which type of unit is installed?
9.I
[E-01]
Which type of compressor is installed?
9.I
[E-02]
What is the indoor unit software type?
9.I
[E-03]
What is the number of backup heater steps?
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*
Range, step
Default value
R/W
18~22°C, step: 1°C
22°C
R/W
1~18°C, step: 1°C
18°C
R/W
[3-07]~[3-06]°C, step: 0,5°C
23°C
R/W
[3-09]~[3-08]°C, step: 0,5°C
23°C
R/W
1~6°C, step: 0,5°C
1 °C
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6 80% pump speed during sampling
6
R/W
0: Solar priority
1: Heat pump priority
0
R/W
0: No
1: Bivalent through header
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step 1°C
3°C
R/W
0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
R/W
0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
R/W
0: LWT control
1: Ext RT control
2: RT control
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
0: Normally open
1: Normally closed
0
0
0
0
0
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
R/W
0: No
1: Active open
2: Active closed
3: Smart grid
R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
R/W
0: No
1: Pwr consmp ctrl
R/W
0: Forced off
1: As normal
R/W (*3)
0: No (*4)
R/O (*4)
1: Solar for DHW (*3)
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
8: 1 pulse/m³ (gas meter)
9: 10 pulses/m³ (gas meter)
10: 100 pulses/m³ (gas meter)
R/W (*4)
0 (*4)
R/O (*3)
2 (*3)
2
0
0
0
R/O
0~5
0: LT split
R/O
1
R/O
0: Reversible (*5)
1: Heating only (*6)
R/O
3: 6V (*1)
4: 9W (*2)
11/13
Installer setting at variance with
default value
Date
Value
4P655201-1 - 2021.09