15.3.5 Symptom: The pump is blocked

Installer reference guide
260
WARNING
Air purging heat emitters or collectors. Before you purge air from heat emitters or
collectors, check if
If not, you can purge air immediately.
If yes, make sure that the room where you want to purge air is sufficiently
ventilated. Reason: Refrigerant might leak into the water circuit, and
subsequently into the room when you purge air from the heat emitters or
collectors.
Possible causes
If the unit has been powered off for a
long time, lime might block the rotor of
the pump.
or
is displayed on the home screen of the user interface.
Depending on the pump type, do one of
the following:
Use a Philips  No.  2 screwdriver to
push the deblocking screw of the
rotor in (0.5  cm). Then turn the
deblocking screw back and forth until
the rotor is deblocked.
Note: Do NOT use excessive force.
1
2
Remove the screw of the stator
housing and use a screwdriver to turn
back and forth the ceramic shaft of
the rotor until the rotor is deblocked.
(a)
Note: Do NOT use excessive force.
1
3
2
Corrective action
(a)
2
2
ERLA11~16DAV3+W1 + EBVH/X11+16S18+23DJ