Symptom: Hot Water Does Not Reach The Desired Temperature; Symptom: The Compressor Does Not Start (Space Heating Or Domestic Water Heating); Symptom: The System Is Making Gurgling Noises After Commissioning; Symptom: The Pump Is Making Noise (Cavitation) - Daikin Altherma EAVX-D9WG Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EAVX-D9WG:
Table of Contents

Advertisement

Possible causes
The water flow is too low
The water volume in the
installation is too low
12.3.2
Symptom: Hot water does NOT reach the
desired temperature
Possible causes
One of the tank temperature
sensors is broken.
12.3.3
Symptom: The compressor does NOT
start (space heating or domestic water
heating)
Possible causes
The unit must start up out of its
operation range (the water
temperature is too low)
EPGA11~16DAV3 + EAVH/X16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556070-1 – 2019.02
Corrective action
Check and make sure that:
▪ All shut-off valves of the water
circuit are completely open.
▪ The water filter is clean. Clean
if necessary.
▪ There is no air in the system.
Purge air if necessary. You
can purge air manually (see
"To perform a manual air
purge" on
page 71) or use the
automatic air purge function
(see
"To perform an automatic
air purge" on
page 71).
▪ The water pressure is >1 bar.
▪ The expansion vessel is NOT
broken.
▪ The valve (if equipped) of the
water
circuit
towards
the
expansion vessel is open.
▪ The resistance in the water
circuit is NOT too high for the
pump (see the ESP curve in
the "Technical data" chapter).
If the problem persists after you
have conducted all of the above
checks, contact your dealer. In
some cases, it is normal that the
unit decides to use a low water
flow.
Make sure that the water volume
in the installation is above the
minimum required value (see
"6.3.3 To check the water volume
and flow rate" on
page 24).
Corrective action
See the service manual of the
unit for the corresponding
corrective action.
Corrective action
If the water temperature is too
low, the unit uses the backup
heater to reach the minimum
water temperature first (15°C).
Check and make sure that:
▪ The
power
supply
to
the
backup
heater
is
correctly
wired.
▪ The backup heater thermal
protector is NOT activated.
▪ The backup heater contactors
are NOT broken.
If the problem persists after you
have conducted all of the above
checks, contact your dealer.
Possible causes
The preferential kWh rate power
supply settings and electrical
connections do NOT match
The preferential kWh rate signal
was sent by the electricity
company
12.3.4
Symptom: The system is making gurgling
noises after commissioning
Possible cause
There is air in the system.
Various malfunctions.
(a)
We recommend to purge air with the unit's air purge
function (to be performed by the installer). If you purge air
from the heat emitters or collectors, mind the following:
WARNING
Air purging heat emitters or collectors. Before you
purge air from heat emitters or collectors, check if
is displayed on the home screen of the user interface.
▪ If not, you can purge air immediately.
▪ If yes, make sure that the room where you want to
purge air is sufficiently ventilated. Reason: Refrigerant
might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.
12.3.5
Symptom: The pump is making noise
(cavitation)
Possible causes
There is air in the system
The water pressure at the pump
inlet is too low
12 Troubleshooting
Corrective action
This should match with the
connections as explained in
"6.4 Preparing electrical
wiring" on page 25
and
"7.6.8 To
connect the main power
supply" on
page 37.
Wait for the power to return (2
hours max.).
Corrective action
(a)
Purge air from the system.
Check if
or
is displayed
on the home screen of the user
interface. See
"12.4.1 To display
the help text in case of a
malfunction" on page 79
for
more information about the
malfunction.
or
Corrective action
Purge air manually (see
"To
perform a manual air purge" on
page 71) or use the automatic air
purge function (see
"To perform
an automatic air purge" on
page 71).
Check and make sure that:
▪ The water pressure is >1 bar.
▪ The water pressure sensor is
not broken.
▪ The expansion vessel is NOT
broken.
▪ The valve (if equipped) of the
water
circuit
towards
the
expansion vessel is open.
▪ The pre-pressure setting of the
expansion vessel is correct
(see
"6.3.4  Changing the pre-
pressure of the expansion
vessel" on
page 25).
Installer reference guide
77